Connection cross section |
|
(rigid/flexible) with cable end sleeve with collar according to DIN 46 228/1 |
0.25 ... 0.75 mm² |
(rigid/flexible) |
0.13 ... 1.5 mm² |
(rigid/flexible) with cable end sleeve according to DIN 46 228/1 |
0.25 ... 1.5 mm² |
Rated insulation voltage Ui |
30 V |
Rated impulse withstand voltage Uimp |
1.5 kV |
Discrepancy time |
|
between FO1A and FO1B |
max. 10 ms |
Utilization category |
|
DC-13 |
24V 200mA |
Risk time according to EN 60947-5-3 |
max. 350 ms |
Risk time according to EN 60947-5-3, extension for each additional device |
max. 5 ms |
Safety class |
III |
Transponder coding |
Unicode |
Degree of contamination (external, according to EN 60947-1) |
3 |
|
Solenoid control input IMP1, IMP2, IMM |
Test pulse duration |
max. 5 ms |
Test pulse interval |
min. 100 ms |
|
Controls and indicators |
Breaking capacity |
max. 0.25 W |
Switching voltage |
UA V |
Switching current |
1 ... 10 mA |
LED power supply |
24 V DC |
|
Emergency stop |
Breaking capacity |
max. 0.25 W |
Switching voltage |
5 ... 24 V |
Switching current |
1 ... 100 mA |
LED power supply |
24 V DC |
|
Monitoring outputs OD, OT, OL, OI |
Output type |
Semiconductor outputs, p-switching, short circuit-proof |
Output voltage |
UA-2V ... UA V DC |
Output current |
max. 50 mA |
|
Safety outputs FO1A, FO1B |
Output type |
Semiconductor outputs, p-switching, short circuit-proof |
Output voltage |
|
UFO1A /UFO1B HIGH |
UB-2V ... UB V DC |
UFO1A /UFO1B LOW |
0 ... 1 V DC |
Output current |
|
per safety output FO1A / FO1B |
1 ... 200 mA |
Test pulse duration |
max. 1 ms |
Test pulse interval |
min. 100 ms |
|
Power supply UA |
Operating voltage DC |
|
UA |
24 V DC -15% ... +10% |
Current consumption |
|
IUA |
max. 375 mA |
|
Power supply UB |
Operating voltage DC |
|
UB |
24 V DC -15% ... +10% |
Current consumption |
|
IUB |
max. 80 mA |