Klemsan Power factor Controller 111R 1 phase ; 606073
RAPIDUS 1 series is a monophase Reactive Power Control Relay. It has 4, 6, 8, 10 and 12-steps options and an optional RS485 port. The built-in temperature sensor...
RAPIDUS 1 series is a monophase Reactive Power Control Relay. It has 4, 6, 8, 10 and 12-steps options and an optional RS485 port. The built-in temperature sensor measures the panel temperature and the fan output can be controlled by the relay outputs.
A power factor controller RAPIDUS is an automation device which allows power distribution system to operate at its maximum efficiency with reducing reactive power. This control process reduces the load requirement on the energy generation and transmission supply system.
· Modular design
· No socket cable required
· Dynamic capacitator monitoring
· The latest technology
· Learning connections and step powers
· Modbus communication
More about product in technical specification and documentation.
General | Measuring system | 1Ø | |
LCD Screen | ✔ | ||
Language Support | Turkish, English | ||
Password Protection | ✔ | ||
Current Transformer Ratio | 1 - 5.000 | ||
Voltage Transformer Ratio | 1 - 999.9 | ||
Connection Type | L-L/L-N | ||
Number of Measurements in a Period | 512 | ||
LCD/Display Refresh Period | <0.5 sec. | ||
Networks | TT, TN, | ||
Signal Waveforms | |||
Control Operations and Functions | Compensation Modes | Rapidus (Intelligent control mode) | ✔ |
Manual | ✔ | ||
Step Configurations | Manually Assigned | ✔ | |
Predefined | 1-1-1-1, 1-2-2-2, 1-2-4-4 | ||
Power (kVAr) | 0.00-1000 adjustable | ||
Type | 3Ø capacitor, 1Ø capacitor | ||
Power Factor Settings | Target 1 cosØ | 0.8 cap. to 0.8 ind. adjustable | |
Target 2 cosØ | 0.8 cap. to 0.8 ind. adjustable | ||
Control Operations and Functions | Dual cosØ Target | ✔ | |
4 Quadrant operation for generators | ✔ | ||
Time Delays | Step Activation Time | 1-600 sec. adjustable | |
Step Deactivation Time | 1-600 sec. adjustable | ||
Step Discharge Time | 3-1000 sec. adjustable | ||
Energy Measurement | Multi Sub-Tariffs (Peak, Day and Off-Peak) | ||
1Ø Phase Energy Meters | |||
3Ø Phase Energy Meters | |||
4 Quadrant Reactive Energy Meters | |||
Current Measurement Input | Measurement Range | 10mA-6A AC | |
Overvoltage Category | 300 V Cat III | ||
Measurement Surge Voltage | |||
Power Consumption | <0.2 VA | ||
Intermittent Overload | 100A for 1 sec. | ||
Sampling Frequency between 45-65 Hz | 25.6 kHz | ||
Voltage Measurement Input | Overvoltage Category | 300 V Cat III | |
Measured Range L-N | 120...510V AC ±10% | ||
Measured Range L-L | 120...510V AC ±10% | ||
Measured Frequency Range | 45-65 Hz | ||
Power Consumption | <0.2 VA | ||
Sampling Frequency between 45-65 Hz | 25.6 kHz | ||
Power Quality Measurements | THD - Voltage in % | ✔ | |
THD - Current in % | ✔ | ||
Measurement Accuracy | According to IEC 61557-12 | Total Active Power | Class 0.5 |
Total Reactive Power | Class 1 | ||
Total Apparent Power | Class 0.5 | ||
Total Active Energy | Class 0.5 | ||
Total Reactive Energy | Class 2 | ||
Frequency | Class 0.1 | ||
Current | Class 0.5 | ||
Neutral Current | Class 0.5 | ||
Voltage | Class 0.2 | ||
Power Factor | Class 0.5 | ||
THDV, THDI | Class 1 | ||
According to IEC 62053-22 | Total Active Energy | Class 0.5S | |
According to IEC 62053-23 | Total Reactive Energy | Class 2 | |
Input and Outputs | Compensation Relay Outputs | Number of outputs | 12 |
Type | NO (SPST) | ||
Max. Switching Current | 2A | ||
Max. Switching Voltage | 250VAC | ||
Max. Switching Power | 1250VA | ||
Mechanical Lifetime | ≥ 10.0000000 operations | ||
Electrical Lifetime Operations (for NO side) | 5×104(5A@250VAC) 1×105(5A@30VDC) | ||
Alarm Relay Outputs | Number of outputs | 2 | |
Type | NO (SPST) | ||
Max. Switching Current | 4A | ||
Max. Switching Voltage | 250 VAC | ||
Max. Switching Power | 1250 VA | ||
Mechanical life time | ≥ 10.0000000 operations | ||
Electrical life time operations (for NO side) | 5×104(5A@250VAC) 1×105(5A@30VDC) | ||
Generator/ Day-Night Input | Number of Inputs | 1 | |
Frequency | 45-65Hz | ||
Input Present or Not | 95-240VAC | ||
Input and Outputs | Digital Outputs | --- | |
Analog Outputs | --- | ||
Supply | Auxilary Supply Input | --- | |
Voltage | La-Lb'den 120...510V AC ±10% | ||
Frequency | 45-65Hz | ||
Supply | Consumption | AC | < 10VA |
DC | --- | ||
Communication | Protocol | Modbus RTU | |
Baud rate | 1200-38400 bps adjustable | ||
Parity number | --- | ||
Stop bit | 1 | ||
Address | 1-247 | ||
Isolation | 2000V RMS | ||
Mechanical Properties | Weight (g) | ||
Protection Class | Front IP40 / Rear IP20 | ||
Mounting Type | Panel Mount | ||
Packing Unit | 1 | ||
Cable Cross Sections | Voltage, Current, All Relay Outputs, Gen Input | Stranded: | 2.5mm² - 14AWG |
Solid: | 4mm² - 12AWG, 2x1.5mm² - 2x16AWG | ||
RS 485 | Stranded: | 1.5mm² - 16AWG | |
Solid: | 1.5mm² - 16AWG, 2x0.75mm² - 2x18AWG | ||
Ambient Conditions | Operating Temperature | -20°C +55°C | |
Storing Temperature | -30°C +80°C | ||
Relative Humidity (no condensation) | Maks. 95% | ||
EMC-EMI | EN 61000-6-1:2011 | ✔ | |
EN 61000-6-3/A1/ AC:2013 | ✔ | ||
Schematics | Network Connections | ✔ | |
Step Output Connections | ✔ | ||
Digital I/O and Alarm Output Connections |
Similar products:
Klemsan Power Factor Controller 116R 1phase ; 606063
(Out of stock)
Klemsan Power Factor Controller 211R 1 phase ; 606011
(Out of stock)
Klemsan Power Factor Controller 218R 1 phase ; 606021
(Out of stock)
Klemsan Power Factor Controller 116R 1phase ; 606063
(Out of stock)
Klemsan Power Factor Controller 211R 1 phase ; 606011
(Out of stock)
Klemsan Power Factor Controller 232R 3phase ; 606002
(Out of stock)