NOVUS N1540 USB 24V Universal Indicator, 2 relays, 4-20 mA, 96x48mm (1/8 DIN); 8154000230
NOVUS N1540 USB 24V Universal Indicator, 2 relays, 4-20 mA, 96x48mm (1/8 DIN); 8154000230...
VAT-exclusive price: 15.518,58 |
VAT-inclusive price: 18.622,30 |
NOVUS N1540 USB 24V Universal Indicator, 2 relays, 4-20 mA, 96x48mm (1/8 DIN); 8154000230
- Display: LED 7-segment, 5-digit, 17 mm high
- Input Type: Thermocouples J, K, T, N, R, S, B, E, Pt100, 0-20 mA, 4-20 mA, 0-50 mV, 0-5 Vdc, 0-10 Vdc.
- Accuracy: Thermocouples J, K, T: 0.2% of span ± 1 ° C; Thermocouple N, R, S, B: 0.2% of span ± 3 ° C; - --- Pt100, 0-20 mA, 4-20 mA, 0- 5 Vdc, 0-10 Vdc: 0.2% of span
- Sampling Rate: Up to 55 per second
- Input resolution: 15 bits
- Analog Output: 0-20 mA or 4-20 mA (optional) - electrically isolated
- Output Resolution: 12 bits
- Alarm: Two alarms
- Alarm Types: Minimum, maximum, minimum differential, maximum differential, differential out of range, sensor open.
- Auxiliary Power Supply: 24 Vdc
- Optional: Analog output (4-20 mA or 0-20 mA), RS485.
- Communication: RS-485 Modbus RTU optional
- Safety: Password protected configuration
- Configuration Interface: USB type Mini B (powered)
- Power Supply: 100 to 240 Vac / dc (± 10%) or 12 to 24 Vdc / 24 Vac (-10% / +20%)
- Maximum Consumption: 6 VA
- Dimensions : 96 x 48 x 34 mm (1/8 DIN)
- Front Panel: IP65; Polycarbonate (PC) UL94 V-2
- Enclosure: IP30; PC UL94 V-2
- Operating Conditions: 0 to 50 ° C, and 0 to 80% RH up to 30 °C
- Input Type: Thermocouples J, K, T, N, R, S, B, E, Pt100, 0-20 mA, 4-20 mA, 0-50 mV, 0-5 Vdc, 0-10 Vdc.
- Accuracy: Thermocouples J, K, T: 0.2% of span ± 1 ° C; Thermocouple N, R, S, B: 0.2% of span ± 3 ° C; - --- Pt100, 0-20 mA, 4-20 mA, 0- 5 Vdc, 0-10 Vdc: 0.2% of span
- Sampling Rate: Up to 55 per second
- Input resolution: 15 bits
- Analog Output: 0-20 mA or 4-20 mA (optional) - electrically isolated
- Output Resolution: 12 bits
- Alarm: Two alarms
- Alarm Types: Minimum, maximum, minimum differential, maximum differential, differential out of range, sensor open.
- Auxiliary Power Supply: 24 Vdc
- Optional: Analog output (4-20 mA or 0-20 mA), RS485.
- Communication: RS-485 Modbus RTU optional
- Safety: Password protected configuration
- Configuration Interface: USB type Mini B (powered)
- Power Supply: 100 to 240 Vac / dc (± 10%) or 12 to 24 Vdc / 24 Vac (-10% / +20%)
- Maximum Consumption: 6 VA
- Dimensions : 96 x 48 x 34 mm (1/8 DIN)
- Front Panel: IP65; Polycarbonate (PC) UL94 V-2
- Enclosure: IP30; PC UL94 V-2
- Operating Conditions: 0 to 50 ° C, and 0 to 80% RH up to 30 °C
Similar products:
NOVUS N1540 USB Universal Indicator, 2 relays, 96x48mm (1/8 DIN); 8154000020
NOVUS N1540 USB Universal Indicator, 2 relays, 96x48mm (1/8 DIN); 8154000020
-
(In stock)
12.344,33
NOVUS N1540 USB 24V Universal Input Panel Meter, 2 relays, 96x48 mm; 8154000030
N1540 USB 24V Universal Input Panel Meter, 2 relays, 96x48 mm; 8154000030
-
(Out of stock)
12.814,59
NOVUS N1540 USB Universal Indicator, 2 relays, 4-20 mA, 96x48mm (1/8 DIN); 8154000220
NOVUS N1540 USB Universal Indicator, 2 relays, 4-20 mA, 96x48mm (1/8 DIN); 8154000220
-
(In stock)
14.225,37
NOVUS N1540 USB RS485 Universal Indicator, 2 relays, 96x48mm (1/8DIN); 8154000320
NOVUS N1540 USB RS485 Universal Indicator, 2 relays, 96x48mm (1/8DIN); 8154000320
-
(In stock)
19.398,23
NOVUS N1540 USB RS485 24V Universal Input Panel Meter, 2 relays, 96x48 mm; 8154000330
N1540 USB RS485 24V Universal Input Panel Meter, 2 relays, 96x48 mm; 8154000330
-
(Out of stock)
20.691,44