Schneider Electric Kontroler M241 24 IO tranzistorski PNP Ethernet; TM241CE24T
Schneider Controller M241 24 IO transistor PNP Ethernet...
Out of stock
Schneider Controller M241 24 IO transistor PNP Ethernet
range of product |
Modicon M241
|
|
---|---|---|
product or component type |
Logic controller
|
|
[Us] rated supply voltage |
24 V DC
|
|
discrete input number |
14, discrete input 8 fast input conforming to IEC 61131-2 Type 1
|
|
discrete output type |
Transistor
|
|
discrete output number |
10 transistor 4 fast output
|
|
discrete output voltage |
24 V DC for transistor output
|
|
discrete output current |
0.5 A for transistor output (Q0...Q9)
0.1 A for fast output (PTO mode) (Q0...Q3) |
discrete I/O number |
24
|
|
---|---|---|
maximum number of I/O expansion module |
7 (local)
14 (remote) |
|
supply voltage limits |
20.4…28.8 V
|
|
inrush current |
50 A
|
|
power consumption in W |
32.6…40.4 W (with max number of I/O expansion module)
|
|
discrete input logic |
Sink or source
|
|
discrete input voltage |
24 V
|
|
discrete input voltage type |
DC
|
|
voltage state 1 guaranteed |
>= 15 V for input
|
|
voltage state 0 guaranteed |
<= 5 V for input
|
|
discrete input current |
5 mA for input
10.7 mA for fast input |
|
input impedance |
4.7 kOhm for input
2.81 kOhm for fast input |
|
response time |
50 µs turn-on, I0...I13 terminal(s) for input
50 µs turn-off, I0...I13 terminal(s) for input <= 2 µs turn-on, I0...I7 terminal(s) for fast input <= 2 µs turn-off, I0...I7 terminal(s) for fast input <= 34 µs turn-on, Q0...Q9 terminal(s) for output <= 250 µs turn-off, Q0...Q9 terminal(s) for output <= 2 µs turn-on, Q0...Q3 terminal(s) for fast output <= 2 µs turn-off, Q0...Q3 terminal(s) for fast output |
|
configurable filtering time |
1 µs for fast input
12 ms for fast input 0 ms for input 1 ms for input 4 ms for input 12 ms for input |
|
discrete output logic |
Positive logic (source)
|
|
output voltage limits |
30 V DC
|
|
maximum current per output common |
2 A with Q0...Q3 for fast output
2 A with Q4...Q7 for output 1 A with Q8...Q9 for output |
|
maximum output frequency |
20 kHz for fast output (PWM mode)
100 kHz for fast output (PLS mode) 1 kHz for output |
|
accuracy |
+/- 0.1 % at 0.02…0.1 kHz for fast output
+/- 1 % at 0.1…1 kHz for fast output |
|
maximum leakage current |
5 µA for output
|
|
maximum voltage drop |
<1 V
|
|
maximum tungsten load |
<2.4 W
|
|
protection type |
Short-circuit protection
Short-circuit and overload protection with automatic reset Reverse polarity protection for fast output |
|
reset time |
10 ms automatic reset output
12 s automatic reset fast output |
|
memory capacity |
8 MB for program
64 MB for system memory RAM |
|
data backed up |
128 MB built-in flash memory for backup of user programs
|
|
data storage equipment |
<= 16 GB SD card (optional)
|
|
battery type |
BR2032 lithium non-rechargeable, battery life: 4 year(s)
|
|
backup time |
2 years at 25 °C
|
|
execution time for 1 KInstruction |
0.3 ms for event and periodic task
0.7 ms for other instruction |
|
application structure |
8 external event tasks
8 event tasks 3 cyclic master tasks + 1 freewheeling task 4 cyclic master tasks |
|
realtime clock |
With
|