Schneider Electric Prekidač ComPacT NSX630F, 36 kA na 415 VAC, MicroLogic 2.3 M zaštitna jedinica 500 A, 3P 3d;C63F32M500
Circuit breaker, ComPacT NSX630F, 36kA/415VAC, 3 poles, MicroLogic 2.3M trip unit 500A...
VAT-exclusive price: 165.714,00 |
VAT-inclusive price: 198.856,80 |
Circuit breaker, ComPacT NSX630F, 36kA/415VAC, 3 poles, MicroLogic 2.3M trip unit 500A
range | ComPacT new generation |
---|---|
product name | ComPacT NSX new generation |
device short name | NSX630F |
product or component type | Circuit breaker |
device application | Motor protection |
poles description | 3P |
protected poles description | 3D |
[In] rated current | 500 A at 65 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
network type | AC |
network frequency | 50/60 Hz |
suitability for isolation | Yes conforming to EN/IEC 60947-2 |
utilisation category | Category A |
[Icu] rated ultimate short-circuit breaking capacity |
40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 600 V AC 50/60 Hz conforming to UL 508 |
Performance level | F 36 kA 415 V AC |
trip unit name | Micrologic 2.3 M |
trip unit technology | Electronic |
trip unit protection functions | LSoI |
control type | Toggle |
Circuit breaker mounting mode | Fixed |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz |
---|---|
[Uimp] rated impulse withstand voltage | 8 kV |
[Ics] rated service short-circuit breaking capacity |
40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
mechanical durability | 15000 cycles |
electrical durability |
8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In |
power dissipation per pole | 25 W |
mounting support | Backplate |
mounting position |
Horizontal and vertical Flat on the back |
upside connection | Front |
downside connection | Front |
connection pitch | 45 mm |
protection type |
L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection |
trip unit rating | 500 A at 65 °C |
motor tripping class |
20 10 5 |
complementary motor protection | Phase unbalance |
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
[Ir] long-time protection pick-up adjustment range | 250...500 A |
Long-time protection delay adjustment type tr | Fixed |
[tr] long-time protection delay adjustment range |
120 s at 1.5 x Ir for trip class 5 6.5 s at 6 x Ir for trip class 5 5 s at 7.2 x Ir for trip class 5 240 s at 1.5 x Ir for trip class 10 13.5 s at 6 x Ir for trip class 10 10 s at 7.2 x Ir for trip class 10 480 s at 1.5 x Ir for trip class 20 26 s at 6 x Ir for trip class 20 20 s at 7.2 x Ir for trip class 20 |
thermal memory | 20 minutes before and after tripping |
Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
[Isd] Short-time protection pick-up adjustment range | 5...13 x Ir |
Short-time protection delay adjustment type tsd | Fixed |
Instantaneous protection pick-up adjustment type Ii | Fixed |
[Ii] instantaneous protection pick-up adjustment range | 6500 A |
earth-leakage protection | Without |
zone selective interlocking ZSI | Without |
Number of slots for electrical auxiliaries | 6 slot(s) |
local signalling |
Flashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point |
Width (W) | 140 mm |
Height (H) | 255 mm |
Depth (D) | 110 mm |
net weight | 6.2 kg |
standards | EN/IEC 60947 |
---|---|
product certifications |
CCC EAC Marine |
overvoltage category | Class II |
electrical shock protection class | Class II |
pollution degree | 3 conforming to IEC 60664-1 |
IP degree of protection | IP40 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 62262 |
ambient air temperature for operation | -25…70 °C |
ambient air temperature for storage | -50…85 °C |
relative humidity | 0…95 % |
operating altitude |
0...2000 m without derating 2000 m...5000 m with derating |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Weight | 5.759 kg |
Package 1 Height | 23.2 cm |
Package 1 width | 16.6 cm |
Package 1 Length | 31.5 cm |