Schneider Electric Temperaturni predajnik - 0..500 °C/32..932 °F - za Optimum Pt100 sonde; RMPT73BD
Converter for Optimum Pt100 probes, Harmony Analog, temperature transmitter, 0...500 degree COr 32...932 degree F...
Price on request
Converter for Optimum Pt100 probes, Harmony Analog, temperature transmitter, 0...500 degree COr 32...932 degree F
Range of product | Harmony Analog |
---|---|
Product or component type | Converter for Optimum Pt100 probes |
Analogue input type | Temperature probe 0...500 °C/32...932 °F Pt 100 2, 3 or 4 wires |
Analogue output type |
Current 4...20 mA <= 500 Ohm Voltage 0...10 V >= 100 kOhm |
Protection type |
Overvoltage protection on output (+/- 30 V) Reverse polarity protection on power supply Short-circuit protection on output Reverse polarity protection on output |
---|---|
abnormal analogue output voltage |
-15...-11 V when no input or input wire broken 11...15 V when no input or input wire broken |
abnormal analogue output current |
-30…0 mA when no input or input wire broken 22…30 mA when no input or input wire broken |
[Us] rated supply voltage | 24 V DC non isolated +/- 20 % |
Current consumption |
<= 40 mA for voltage output <= 60 mA for current output |
Local signalling | LED (green) for power ON |
Measurement error |
+/- 0.5 % of full scale (3 or 4 wires) at 20 °C +/- 1 % of full scale (2 wires) at 20 °C +/- 10 % of full scale at 20 °C (electromagnetic interference of 10 V/m) |
Repeat accuracy |
+/- 0.2 % full scale at 20 °C +/- 0.6 % full scale at 60 °C |
Temperature coefficient | 150 ppm/°C |
Maximum wiring resistance | 0.2 Ohm connection in 2 wires |
Clamping connection capacity |
2 x 1.5 mm² 1 x 2.5 mm² |
Tightening torque | 0.6…1.1 N.m |
Marking | CE |
Surge withstand | 0.5 kV during 1.2/50 µs conforming to IEC 61000-4-5 |
[Ui] rated insulation voltage | 2000 V |
Fixing mode |
Clip-on (35 mm symmetrical DIN rail) Fixed (mounting plate) |
Safety reliability data |
MTTFd = 43.9 years B10d = 40564 |
Net weight | 0.12 kg |
Electromagnetic compatibility |
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 |
---|---|
Standards |
DIN 43760 EN/IEC 60584-1 EN/IEC 60947-1 EN/IEC 60751 |
Product certifications |
GL UL CSA |
IP degree of protection |
IP20 (terminal block) IP50 (housing) |
Fire resistance |
850 °C conforming to IEC 60695-2-1 850 °C conforming to UL |
Shock resistance | 50 gn for 11 ms conforming to IEC 60068-2-27 |
Vibration resistance | 5 gn (f= 10…100 Hz) conforming to IEC 60068-2-6 |
Resistance to fast transients |
1 kV (on input-output) conforming to IEC 61000-4-4 2 kV (on power supply) conforming to IEC 61000-4-4 |
Disturbance radiated/conducted |
CISPR 11 CISPR 22 group 1 - class B |
Ambient air temperature for storage | -40…85 °C |
Ambient air temperature for operation |
0…50 °C mounting side by side 0…60 °C 2 cm spacing |
Pollution degree | 2 conforming to IEC 60664-1 |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 2.7 cm |
Package 1 Width | 8.2 cm |
Package 1 Length | 8.5 cm |
Package 1 Weight | 109.0 g |
Unit Type of Package 2 | S02 |
Number of Units in Package 2 | 47 |
Package 2 Height | 15.0 cm |
Package 2 Width | 30.0 cm |
Package 2 Length | 40.0 cm |
Package 2 Weight | 5.214 kg |
Warranty | 18 months |
---|