Schneider Electric TeSys LRD termički relej - 30...38 A - klasa 10A ; LRD35
TeSys LRD thermal overload relays - 30...38 A - class 10A...
VAT-exclusive price: 10.151,00 |
VAT-inclusive price: 12.181,20 |
TeSys LRD thermal overload relays - 30...38 A - class 10A
range |
TeSys
|
|
---|---|---|
product name |
TeSys LRD
|
|
product or component type |
Differential thermal overload relay
|
|
device short name |
LRD
|
|
relay application |
Motor protection
|
|
product compatibility |
LC1D32
LC1D38 |
|
network type |
DC
AC |
|
thermal overload class |
Class 10A conforming to IEC 60947-4-1
|
|
thermal protection adjustment range |
30…38 A
|
|
[Ui] rated insulation voltage |
Power circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL Power circuit: 690 V conforming to IEC 60947-4-1 |
network frequency |
0...400 Hz
|
|
---|---|---|
mounting support |
Plate, with specific accessories
Rail, with specific accessories Under contactor |
|
tripping threshold |
1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
|
|
auxiliary contact composition |
1 NO + 1 NC
|
|
[Ith] conventional free air thermal current |
5 A for signalling circuit
|
|
permissible current |
1.5 A at 240 V AC-15 for signalling circuit
0.1 A at 250 V DC-13 for signalling circuit |
|
[Ue] rated operational voltage |
690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
|
|
associated fuse rating |
4 A gG for signalling circuit
4 A BS for signalling circuit |
|
[Uimp] rated impulse withstand voltage |
6 kV
|
|
phase failure sensitivity |
Tripping current 130 % of Ir on two phase, the last one at 0
|
|
control type |
Red push-button: stop
Blue push-button: reset |
|
temperature compensation |
-20…60 °C
|
|
connections - terminals |
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² solid without cable end |
|
tightening torque |
Control circuit: 1.7 N.m - on screw clamp terminals
Power circuit: 2.5 N.m - on screw clamp terminals |
|
height |
66 mm
|
|
width |
45 mm
|
|
depth |
70 mm
|
|
net weight |
0.124 kg
|
protective treatment |
TH conforming to IEC 60068
|
|
---|---|---|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
ambient air temperature for operation |
-20…60 °C without derating conforming to IEC 60947-4-1
|
|
ambient air temperature for storage |
-60…70 °C
|
|
flame retardance |
V1 conforming to UL 94
|
|
mechanical robustness |
Vibrations: 6 Gn conforming to IEC 60068-2-6
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7 |
|
dielectric strength |
1.89 kV at 50 Hz conforming to IEC 60947-1
|
|
standards |
EN/IEC 60947-4-1
EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 GB/T 14048.4 GB/T 14048.5 EN 50495 |
|
product certifications |
IEC
UL CSA CCC EAC BV RINA DNV-GL LROS (Lloyds register of shipping) ATEX INERIS |
Unit Type of Package 1 |
PCE
|
|
---|---|---|
Number of Units in Package 1 |
1
|
|
Package 1 Weight |
140 g
|
|
Package 1 Height |
4.9 cm
|
|
Package 1 width |
7.8 cm
|
|
Package 1 Length |
9 cm
|
|
Unit Type of Package 2 |
S02
|
|
Number of Units in Package 2 |
24
|
|
Package 2 Weight |
3.686 kg
|
|
Package 2 Height |
15 cm
|
|
Package 2 width |
30 cm
|
|
Package 2 Length |
40 cm
|
|
Unit Type of Package 3 |
P06
|
|
Number of Units in Package 3 |
384
|
|
Package 3 Weight |
72.372 kg
|
|
Package 3 Height |
80 cm
|
|
Package 3 width |
80 cm
|
|
Package 3 Length |
60 cm
|
Sustainable offer status |
Green Premium product
|
|
---|---|---|
REACh Regulation | ||
REACh free of SVHC |
Yes
|
|
EU RoHS Directive |
Compliant
EU RoHS Declaration |
|
Mercury free |
Yes
|
|
RoHS exemption information | ||
China RoHS Regulation |
China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information |
|
Environmental Disclosure | ||
Circularity Profile | ||
WEEE |
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
Warranty |
18 months
|
---|
Similar products:
Schneider Electric TeSys LRD termički relej - 0.4...0.63 A - klasa 10A; LRD04
TeSys Deca thermal overload relays,0.4...0.63A,class 10A
-
(Out of stock)
6.676,00
Schneider Electric TeSys LRD termički relej - 0.63...1 A - klasa 10A; LRD05
TeSys Deca thermal overload relays,0.63...1A,class 10A
-
(Out of stock)
6.676,00
Schneider Electric TeSys LRD termički relej - 1...1.6 A - klasa 10A;LRD06
Thermal overload relay, TeSys Deca, 690VAC, 1 to 1.6A, 1NO+1NC, class 10A, screw clamp
-
(Out of stock)
6.676,00
Schneider Electric TeSys LRD termički relej - 30...38 A - klasa 10A ; LRD356
TeSys LRD thermal overload relays - 30...38 A - class 10A
-
(Out of stock)
11.576,00
Schneider Electric TeSys LRD termički relej - 55...70 A - klasa 20 ; LR2D3561
TeSys LRD thermal overload relays - 55...70 A - class 20
-
(Out of stock)
30.751,00
Schneider Electric TeSys LRD - elektronski termički relej - 60...100 A - klasa 10...20; LR9D67
electronic thermal overload relay, TeSys Deca, 60...100A, class 10...20; LR9D67
-
(Out of stock)
43.218,00