Trip unit MicroLogic 6.3E, ComPacT NSX630, 3 poles, electronic basic and ground fault protections, energy meter, 630A
Main
range |
ComPacT new generation |
range of product |
ComPacT NSX400...630 new generation |
product or component type |
Trip unit |
trip unit name |
Micrologic 6.3 E |
trip unit technology |
Electronic |
range compatibility |
ComPacT new generation NSX630 |
device application |
Distribution |
poles description |
3P |
protected poles description |
3D |
trip unit protection functions |
LSIG |
protection type |
L : for overload protection (long time)
S : for short time short-circuit protection
I : for instantaneous short-circuit protection
G : for ground fault protection |
Trip unit rating |
630 A at 40 °C |
[Ue] rated operational voltage |
690 V AC 50/60 Hz |
network type |
AC |
network frequency |
50/60 Hz |
Circuit breaker mounting mode |
Fixed |
Complementary
Long-time pick-up adjustment type Ir (thermal protection) |
Adjustable |
[Ir] long-time protection pick-up adjustment range |
250...630 A |
Long-time protection delay adjustment type tr |
Adjustable |
[tr] long-time protection delay adjustment range |
15…400 s at 1.5 x Ir
0.35…11 s at 7.2 x Ir
0.5…16 s at 6 x Ir |
thermal memory |
20 minutes before and after tripping |
Short-time protection pick-up adjustment type Isd |
Adjustable |
[Isd] Short-time protection pick-up adjustment range |
1.5...10 x Ir |
Short-time protection delay adjustment type tsd |
Adjustable |
[tsd] Short-time protection delay adjustment range |
0…0.4 s I²t=off
0.1…0.4 s I²t=on |
Instantaneous protection pick-up adjustment type Ii |
Adjustable |
[Ii] instantaneous protection pick-up adjustment range |
1.5...11 x In |
Ground-fault protection pick-up adjustment type Ig |
Adjustable |
[Ig] ground-fault protection pick-up adjustment range |
0.4...1 x In for In = 40 A
0.2...1 x In for In > 40 A
Ig enable on/off |
Ground-fault protection time delay adjustment type tg |
Adjustable |
[tg] ground-fault protection time delay adjustment range |
0…0.4 s I²t=off
0.1…0.4 s I²t=on |
earth-leakage protection |
Without |
zone selective interlocking ZSI |
With |
local signalling |
Flashing LED (green) for ready to operate
LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overload |
display type |
LCD display |
type of measurement |
Energy meter |
communication of data |
Energy metering
Protection and alarm settings
Time-stamped histories and event tables
Instantaneous and demand values
Maintenance indicators
Demand current and power
Power quality
Maximeters/minimeters |
electrical data recording |
Maintenance indicators |
Environment
standards |
EN/IEC 60947-2 |
electrical shock protection class |
Class II |
pollution degree |
3 conforming to IEC 60947-1 |
IP degree of protection |
IP40 conforming to IEC 60529 |
ambient air temperature for operation |
-25…70 °C |
ambient air temperature for storage |
-40…85 °C |
Packing Units
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Weight |
1.48 kg |
Package 1 Height |
13.5 cm |
Package 1 width |
17.5 cm |
Package 1 Length |
21.5 cm |
Unit Type of Package 2 |
S03 |
Number of Units in Package 2 |
4 |
Package 2 Weight |
6.376 kg |
Package 2 Height |
30.0 cm |
Package 2 width |
30.0 cm |
Package 2 Length |
40.0 cm |