Siemens ET 200SP, reversing starter 2.8 - 9 A HF; 3RK1308-0BD00-0CP0
Reversing starter High Feature; Electronic switching; Electronic overload protection up to 4 kW / 400 V; Adjustment range 2.8 .. 9 A; PROFIenergy; Option: 3DI/LC...
Price on request
product brand name | SIMATIC |
product category | Motor starter |
product designation | Reversing starter |
product type designation | ET 200SP |
General technical data | |
trip class | CLASS OFF / 5 / 10 adjustable |
equipment variant according to IEC 60947-4-2 | 3 |
product function | Reversing starter |
● on-site operation | Yes |
● intrinsic device protection | Yes |
● remote firmware update | Yes |
● for power supply reverse polarity protection | Yes |
insulation voltage rated value | 500 V |
degree of pollution | 2 |
overvoltage category | III |
surge voltage resistance rated value | 6 kV |
maximum permissible voltage for safe isolation | |
● between main and auxiliary circuit | 500 V |
shock resistance | 6g / 11 ms |
vibration resistance | 15 mm to 6 Hz; 2g to 500 Hz |
operating frequency maximum | 1 1/s |
mechanical service life (switching cycles) of the main contacts typical | 30 000 000 |
type of assignment | 1 |
utilization category | |
● according to IEC 60947-4-2 | AC-53a: 9 A: (8-0,7: 70-32) |
reference code according to IEC 81346-2 | Q |
Substance Prohibitance (Date) | 04/15/2016 |
product function | |
● direct start | Yes |
● reverse starting | Yes |
product component motor brake output | No |
product function short circuit protection | Yes |
design of short-circuit protection | fuse |
breaking capacity maximum short-circuit current (Icu) | |
● at 400 V rated value | 55 kA |
● at 500 V rated value | 55 kA |
● at 500 V according to UL 60947 rated value | 100 kA |
breaking capacity maximum short-circuit current (Icu) in the IT network | |
● at 400 V rated value | 55 kA |
● at 500 V rated value | 55 kA |
Electromagnetic compatibility | |
EMC emitted interference according to IEC 60947-1 | class A |
EMC immunity according to IEC 60947-1 | Class A |
conducted interference | |
● due to burst according to IEC 61000-4-4 | 2 kV |
● due to conductor-earth surge according to IEC 61000-4-5 | 2 kV |
● due to conductor-conductor surge according to IEC 61000-4-5 | 1 kV |
● due to high-frequency radiation according to IEC 61000-4-6 | Class A |
field-based interference according to IEC 61000-4-3 | 10 V/m |
electrostatic discharge according to IEC 61000-4-2 | 8 kV air discharge |
conducted HF interference emissions according to CISPR11 | Class A for industrial environment |
field-bound HF interference emission according to CISPR11 | Class A for industrial environment |
Safety related data | |
MTBF | 46 y |
safe state | Load circuit open |
protection class IP on the front according to IEC 60529 | IP20 |
touch protection on the front according to IEC 60529 | finger-safe |
Main circuit | |
number of poles for main current circuit | 3 |
design of the switching contact | Hybrid |
adjustable current response value current of the current-dependent overload release | 2.8 ... 9 A |
minimum load [%] | 50 %; from smallest adjustable rated current |
type of the motor protection | solid-state |
Similar products:
Siemens ET 200SP, D-O-L starter 0.1 - 0.4A HF; 3RK1308-0AA00-0CP0
Direct-on-line starter High Feature; Electronic switching; Electronic overload protection up to 0.09 kW / 400 V; Adjustment range 0.1 .. 0.4 A; PROFIenergy; Option:
-
(Out of stock)
Price on request
Siemens ET 200SP, reversing starter 0.9 - 3A HF; 3RK1308-0BC00-0CP0
Reversing starter High Feature; Electronic switching; Electronic overload protection up to 1.1 kW / 400 V; Adjustment range 0.9 .. 3 A; PROFIenergy; Option: 3DI/LC
-
(Out of stock)
Price on request
Siemens ET 200SP, reversing starter 4.0 - 12A HF; 3RK1308-0BE00-0CP0
Reversing starter High Feature; Incl. fan (3RW4928-8VB00); Electronic switching; Electronic overload protection up to 5.5 kW / 400 V; Adjustment range 4.0 .. 12
-
(Out of stock)
Price on request
Siemens ET 200SP, reversing starterF 0.1-0.4A HF; 3RK1308-0DA00-0CP0
Failsafe reversing starter High Feature; Electronic switching; Electronic overload protection up to 0.09 kW / 400 V; Adjustment range 0.1 .. 0.4 A; PROFIenergy;
-
(Out of stock)
Price on request
Siemens ET 200SP, reversing starter F 0.3-1A HF; 3RK1308-0DB00-0CP0
Failsafe reversing starter High Feature; Electronic switching; Electronic overload protection up to 0.25 kW / 400 V; Adjustment range 0.3 .. 1 A; PROFIenergy; Option:
-
(Out of stock)
Price on request
Siemens ET 200SP, reversing starter F 0.9-3A HF; 3RK1308-0DC00-0CP0
Failsafe reversing starter High Feature; Electronic switching; electronic overload protection up to 1.1 kW / 400 V; Adjustment range 0.9 .. 3 A; PROFIenergy; option:
-
(Out of stock)
Price on request