Siemens ET 200SP, RQ COni 3x120VDC.230VAC/5A ST; 6ES7132-6HC70-0BU0

Siemens ET 200SP, RQ COni 3x120VDC.230VAC/5A ST; 6ES7132-6HC70-0BU0

SIMATIC ET 200SP, relay module, RQ COni 3x120VDC..230VAC/5A ST, 3 CO contacts non-isolated contacts, packing unit: 1 unit, suitable for BU type U0, color code CC20,...

Brand: Siemens
Product Code: 6ES7132-6HC70-0BU0
Availability: Check availability
Price on request
SIMATIC ET 200SP, relay module, RQ COni 3x120VDC..230VAC/5A ST, 3 CO contacts non-isolated contacts, packing unit: 1 unit, suitable for BU type U0, color code CC20, substitute value output, module diagnostics for supply voltage

Similar products:


Siemens ET 200SP, DQ 8x 24V DC/0,5A ST, PU 1; 6ES7132-6BF01-0BA0

SIMATIC ET 200SP, Digital output module, DQ 8x 24V DC/0,5A Standard, Source output (PNP,P-switching) Packing unit: 1 piece, fits to BU-type A0, Colour Code CC02,
-
In stock

(In stock)

Price on request

Siemens ET 200SP, DQ 16X24VDC/0,5A BA, PU 1; 6ES7132-6BH00-0AA0

SIMATIC ET 200SP, digital output module, DQ 16x 24VDC/0.5A Basic, Pack quantity: 1 unit, suitable for BU type A0, Color code CC00, Module diagnostics
-
Need to order

(Out of stock)

Price on request

Siemens ET 200SP, DQ 8x24VDC/0,5A HF, PU 1; 6ES7132-6BF00-0CA0

SIMATIC ET 200SP, digital output module, DQ 8x 24VDC/0.5A High Feature, source output PNP, source output, Packing unit: 1 unit, suitable for BU type A0, color code
-
Need to order

(Out of stock)

Price on request

Siemens ET 200SP, RQ NO 4x 120VDC..230VAC/5A,PU1; 6ES7132-6HD01-0BB1

SIMATIC ET 200SP, Relay module, RQ NO 4x 120V DC..230VAC/5A ST. 4 normally open contacts, isolated contacts, packing unit: 1 piece, fits to BU-type B0 and B1, Colour
-
Need to order

(Out of stock)

Price on request

Siemens ET 200SP,RQ NO-mA 4x120VDC..230VAC/5A ST; 6ES7132-6MD00-0BB1

SIMATIC ET 200SP, relay module normally open, RQ NO-MA4x120VDC..230VAC/5A ST, with manual operation, packing unit VPE 1, suitable for BU type B0 or B1, Module d
-
Need to order

(Out of stock)

Price on request

Siemens ET 200SP, DQ 16x 24V DC/0,5A ST, PU 1; 6ES7132-6BH01-0BA0

SIMATIC ET 200SP, Digital output module, DQ 16x 24V DC/0,5A Standard, Source output (PNP,P-switching) Packing unit: 1 piece, fits to BU-type A0, Colour Code CC00,
-
In stock

(In stock)

 
 
12.461,89

ELECTRO PNEUMATIC SOLUTIONS DOO

  • Jugoslovenska 2/13A, Čukarica, Beograd
  • Opening Times: Monday - Friday 8am-5pm
  • Telephone:
  • 011 257 1922
  • +381 64 659 66 55
  • +381 62 800 70 44
  • email: office@ep-solutions.rs

linkedin youtube instagram twitter facebook
1
2
3
Compare products Remove all products
General information
Product type designation RQ 3x120VDC-230VAC/5A CO n.i. ST
Firmware version V0.0
● FW update possible No
usable BaseUnits BU type U0
Color code for module-specific color identification plate CC20
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
Redundancy
● Redundancy capability Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption (rated value) 55 mA; without load
output voltage / header
Rated value (AC) 230 V
Power loss
Power loss, typ. 1.4 W
Address area
Address space per module
● Inputs + 1 byte for QI information
● Outputs 1 byte
Hardware configuration
Automatic encoding Yes
● Mechanical coding element Yes
● Type of mechanical coding element type C
Selection of BaseUnit for connection variants
● 2-wire connection BU type U0
● 3-wire connection BU type U0
Digital outputs
Type of digital output Relays
Number of digital outputs 3
Current-sinking Yes
Current-sourcing Yes
Digital outputs, parameterizable Yes
Short-circuit protection No
Switching capacity of the outputs
● with resistive load, max. 5 A; see additional description in the manual
● with inductive load, max. 2 A; see additional description in the manual
Parallel switching of two outputs
● for logic links Yes
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 2 Hz
● with inductive load, max. 0.5 Hz
● on lamp load, max. 2 Hz
Total current of the outputs
● Current per channel, max. 5 A
● Current per module, max. 5 A
Total current of the outputs (per module)
horizontal installation
— up to 50 °C, max. 5 A
— up to 60 °C, max. 5 A
vertical installation
— up to 40 °C, max. 5 A
— up to 50 °C, max. 5 A
Relay outputs
● Number of relay outputs 3; Changeover contact, non-floating
● Rated supply voltage of relay coil L+ (DC) 24 V
● Current consumption of relays (coil current of all relays), max. 40 mA
● external protection for relay outputs yes, with miniature fuse max. 6.3 A tripping current, quick-response tripping characteristic and 1 500 A breaking capacity
● Number of operating cycles, max. 1 000 000; see additional description in the manual
Switching capacity of contacts
— with inductive load, max. 2 A; see additional description in the manual
— with resistive load, max. 5 A; see additional description in the manual
— Thermal continuous current, max. 5 A; Max. 1 385 VA, 150 W
— Switching current, min. 10 mA; 5 V DC
— Rated switching voltage (DC) 24 V DC to 120 V DC
— Rated switching voltage (AC) 24V AC to 230V AC