Siemens S7-1500, AI 8 X U/R/RTD/TC HF; 6ES7531-7PF00-0AB0
SIMATIC S7-1500 analog input module AI 8xU/R/RTD/TC HF, 16 bit resolution, up to 21 bit Resolution at RT and TC, accuracy 0.1%, 8 channels in groups of 1; common...
Price on request
SIMATIC S7-1500 analog input module AI 8xU/R/RTD/TC HF, 16 bit resolution, up to 21 bit Resolution at RT and TC, accuracy 0.1%, 8 channels in groups of 1; common mode voltage: 30 V AC/60 V DC, Diagnostics; Hardware interrupts Scalable temperature measuring range, thermocouple type C, Calibrate in RUN; Delivery including infeed element, shield bracket and shield terminal: Front connector (screw terminals or push-in) to be ordered separately |
General information | |
Product type designation | AI 8xU/R/RTD/TC HF |
HW functional status | FS01 |
Firmware version | V1.1.0 |
● FW update possible | Yes |
Product function | |
● I&M data | Yes; I&M0 to I&M3 |
● Isochronous mode | No |
● Prioritized startup | Yes |
● Measuring range scalable | Yes |
● Scalable measured values | No |
● Adjustment of measuring range | No |
Engineering with | |
● STEP 7 TIA Portal configurable/integrated from version | V14 / - |
● STEP 7 configurable/integrated from version | V5.5 SP3 / - |
● PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
● PROFINET from GSD version/GSD revision | V2.3 / - |
Operating mode | |
● Oversampling | No |
● MSI | Yes |
CiR - Configuration in RUN | |
Reparameterization possible in RUN | Yes |
Calibration possible in RUN | Yes |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current | |
Current consumption, max. | 55 mA; with 24 V DC supply |
Power | |
Power available from the backplane bus | 0.85 W |
Power loss | |
Power loss, typ. | 1.9 W |
Analog inputs | |
Number of analog inputs | 8; Plus one additional RTD (reference) channel |
● For voltage measurement | 8; Plus one additional RTD (reference) channel |
● For resistance/resistance thermometer measurement | 8; Plus one additional RTD (reference) channel |
● For thermocouple measurement | 8; Plus one additional RTD (reference) channel |
permissible input voltage for voltage input (destruction limit), max. | 20 V |
Constant measurement current for resistance-type transmitter, typ. | 150 Ohm, 300 Ohm, 600 Ohm, Cu10, Cu50, Cu100, Ni10, Ni100, Ni120, Ni200, Pt10, Pt50, Pt100, Pt200 climate: 1 mA; 6 kOhm, Ni500, Ni1000, LG-Ni1000, Pt200 standard, Pt500, Pt1000, PTC: 0.25 mA |
Technical unit for temperature measurement adjustable | Yes; °C/°F/K |
Input ranges (rated values), voltages | |
● 0 to +5 V | No |
● 0 to +10 V | No |
● 1 V to 5 V | No |
● -1 V to +1 V | Yes |
— Input resistance (-1 V to +1 V) | 10 MΩ |
● -10 V to +10 V | No |
● -2.5 V to +2.5 V | No |
● -25 mV to +25 mV | Yes |
— Input resistance (-25 mV to +25 mV) | 10 MΩ |
● -250 mV to +250 mV | Yes |
— Input resistance (-250 mV to +250 mV) | 10 MΩ |
● -5 V to +5 V | No |
● -50 mV to +50 mV | Yes |
— Input resistance (-50 mV to +50 mV) | 10 MΩ |
● -500 mV to +500 mV | Yes |
— Input resistance (-500 mV to +500 mV) | 10 MΩ |
● -80 mV to +80 mV | Yes |
— Input resistance (-80 mV to +80 mV) | 10 MΩ |
Input ranges (rated values), currents | |
● 0 to 20 mA | No |
● -20 mA to +20 mA | No |
● 4 mA to 20 mA | No |
Input ranges (rated values), thermocouples | |
● Type B | Yes |
— Input resistance (Type B) | 10 MΩ |
● Type C | Yes |
— Input resistance (Type C) | 10 MΩ |
● Type E | Yes |
— Input resistance (Type E) | 10 MΩ |
● Type J | Yes |
— Input resistance (type J) | 10 MΩ |
● Type K | Yes |
— Input resistance (Type K) | 10 MΩ |
● Type L | No |
● Type N | Yes |
— Input resistance (Type N) | 10 MΩ |
● Type R | Yes |
— Input resistance (Type R) | 10 MΩ |
● Type S | Yes |
— Input resistance (Type S) | 10 MΩ |
● Type T | Yes |
— Input resistance (Type T) | 10 MΩ |
● Type TXK/TXK(L) to GOST | Yes |
— Input resistance (Type TXK/TXK(L) to GOST) | 10 MΩ |
Input ranges (rated values), resistance thermometer | |
● Cu 10 | Yes; Standard/climate |
— Input resistance (Cu 10) | 10 MΩ |
● Cu 10 according to GOST | Yes; Standard/climate |
— Input resistance (Cu 10 according to GOST) | 10 MΩ |
● Cu 50 | Yes; Standard/climate |
— Input resistance (Cu 50) | 10 MΩ |
● Cu 50 according to GOST | Yes; Standard/climate |
— Input resistance (Cu 50 according to GOST) | 10 MΩ |
● Cu 100 | Yes; Standard/climate |
— Input resistance (Cu 100) | 10 MΩ |
● Cu 100 according to GOST | Yes; Standard/climate |
— Input resistance (Cu 100 according to GOST) | 10 MΩ |
● Ni 10 | Yes; Standard/climate |
— Input resistance (Ni 10) | 10 MΩ |
● Ni 10 according to GOST | Yes; Standard/climate |
— Input resistance (Ni 10 according to GOST) | 10 MΩ |
● Ni 100 | Yes; Standard/climate |
— Input resistance (Ni 100) | 10 MΩ |
● Ni 100 according to GOST | Yes; Standard/climate |
— Input resistance (Ni 100 according to GOST) | 10 MΩ |
● Ni 1000 | Yes; Standard/climate |
— Input resistance (Ni 1000) | 10 MΩ |
● Ni 1000 according to GOST | Yes; Standard/climate |
— Input resistance (Ni 1000 according to GOST) | 10 MΩ |
● LG-Ni 1000 | Yes; Standard/climate |
— Input resistance (LG-Ni 1000) | 10 MΩ |
● Ni 120 | Yes; Standard/climate |
— Input resistance (Ni 120) | 10 MΩ |
● Ni 120 according to GOST | Yes; Standard/climate |
— Input resistance (Ni 120 according to GOST) | 10 MΩ |
● Ni 200 | Yes; Standard/climate |
— Input resistance (Ni 200) | 10 MΩ |
● Ni 200 according to GOST | Yes; Standard/climate |
— Input resistance (Ni 200 according to GOST) | 10 MΩ |
● Ni 500 | Yes; Standard/climate |
— Input resistance (Ni 500) | 10 MΩ |
● Ni 500 according to GOST | Yes; Standard/climate |
— Input resistance (Ni 500 according to GOST) | 10 MΩ |
● Pt 10 | Yes; Standard/climate |
— Input resistance (Pt 10) | 10 MΩ |
● Pt 10 according to GOST | Yes; Standard/climate |
— Input resistance (Pt 10 according to GOST) | 10 MΩ |
● Pt 50 | Yes; Standard/climate |
— Input resistance (Pt 50) | 10 MΩ |
● Pt 50 according to GOST | Yes; Standard/climate |
— Input resistance (Pt 50 according to GOST) | 10 MΩ |
● Pt 100 | Yes; Standard/climate |
— Input resistance (Pt 100) | 10 MΩ |
● Pt 100 according to GOST | Yes; Standard/climate |
— Input resistance (Pt 100 according to GOST) | 10 MΩ |
● Pt 1000 | Yes; Standard/climate |
— Input resistance (Pt 1000) | 10 MΩ |
● Pt 1000 according to GOST | Yes; Standard/climate |
— Input resistance (Pt 1000 according to GOST) | 10 MΩ |
● Pt 200 | Yes; Standard/climate |
— Input resistance (Pt 200) | 10 MΩ |
● Pt 200 according to GOST | Yes; Standard/climate |
— Input resistance (Pt 200 according to GOST) | 10 MΩ |
● Pt 500 | Yes; Standard/climate |
— Input resistance (Pt 500) | 10 MΩ |
● Pt 500 according to GOST | Yes; Standard/climate |
— Input resistance (Pt 500 according to GOST) | 10 MΩ |
Input ranges (rated values), resistors | |
● 0 to 150 ohms | Yes |
— Input resistance (0 to 150 ohms) | 10 MΩ |
● 0 to 300 ohms | Yes |
— Input resistance (0 to 300 ohms) | 10 MΩ |
● 0 to 600 ohms | Yes |
— Input resistance (0 to 600 ohms) | 10 MΩ |
● 0 to 3000 ohms | No |
● 0 to 6000 ohms | Yes |
— Input resistance (0 to 6000 ohms) | 10 MΩ |
● PTC | Yes |
— Input resistance (PTC) | 10 MΩ |
Thermocouple (TC) | |
Temperature compensation | |
— parameterizable | Yes |
— internal temperature compensation | Yes |
— external temperature compensation via RTD | Yes |
— Compensation for 0 °C reference point temperature | Yes; fixed value can be set |
— Reference channel of the module | Yes; 9th channel that can be used as a genuine 9th RTD channel regardless of the parameterization of the other channels, or that can be used for compensation in the case of TC measurement |
Cable length | |
● shielded, max. | 800 m; at U; 200 m at R/RTD/TC |
Analog value generation for the inputs | |
Integration and conversion time/resolution per channel | |
● Resolution with overrange (bit including sign), max. | 21 bit; For measuring mode RTC and TC when using the function "Scalable temperature measuring range" (32 bit REAL format); 16 bit for measuring mode R and U; 16 bit for all measuring modes when using the S7 format (16 bit INTEGER) |
● Integration time, parameterizable | Yes |
● Integration time (ms) | Fast mode: 2.5 / 16.67 / 20 / 100 ms, standard mode: 7.5 / 50 / 60 / 300 ms |
● Basic conversion time, including integration time (ms) | Fast mode: 4 / 18 / 22 / 102 ms; Standard mode: 9 / 52 / 62 / 302 ms |
— additional conversion time for wire-break monitoring | Thermocouples, 150 Ohm, 300 Ohm, 600 Ohm, Cu10, Cu50, Cu100, Ni10, Ni100, Ni120, Ni200, Pt10, Pt50, Pt100: 4 ms; 6 kOhm, Ni500, Ni1000, LG-Ni1000, Pt200, Pt500, Pt1000: 13 ms |
● Interference voltage suppression for interference frequency f1 in Hz | 400 / 60 / 50 / 10 Hz |
● Basic execution time of the module (all channels released) | Corresponds to the channel with the highest basic conversion time |
Smoothing of measured values | |
● parameterizable | Yes |
● Step: None | Yes |
● Step: low | Yes |
● Step: Medium | Yes |
● Step: High | Yes |
Encoder | |
Connection of signal encoders | |
● for voltage measurement | Yes |
● for current measurement as 2-wire transducer | No |
● for current measurement as 4-wire transducer | No |
● for resistance measurement with two-wire connection | Yes |
● for resistance measurement with three-wire connection | Yes; All measuring ranges except PTC; internal compensation of the cable resistances |
● for resistance measurement with four-wire connection | Yes; All measuring ranges except PTC |
Errors/accuracies | |
Linearity error (relative to input range), (+/-) | 0.02 % |
Temperature error (relative to input range), (+/-) | 0.005 %/K |
Crosstalk between the inputs, max. | -80 dB |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.02 % |
Temperature error of internal compensation | ±1,5 °C |
Operational error limit in overall temperature range | |
● Voltage, relative to input range, (+/-) | 0.1 % |
● Resistance, relative to input range, (+/-) | 0.1 % |
● Resistance thermometer, relative to input range, (+/-) | Cuxxx Standard: ±0.5 K, Cuxxx Klima: ±0.5 K, Ptxxx Standard: ±1 K, Ptxxx Klima: ±0.5 K, Nixxx Standard: ±0.5 K, Nixxx Klima: ±0.3 K |
● Thermocouple, relative to input range, (+/-) | Type B: > 600 °C ±2 K, Type E: > -200 °C ±1 K, Type J: > -210 °C ±1 K, Type K: > -200 °C ±2 K, Type N: > -200 °C ±2 K, Type R: > 0 °C ±2 K, Type S: > 0 °C ±2 K, Type T: > -200 °C ±1 K, Type C: ±4 K, Type TXK/TXK(L): ±1 K |
Basic error limit (operational limit at 25 °C) | |
● Voltage, relative to input range, (+/-) | 0.05 % |
● Resistance, relative to input range, (+/-) | 0.05 % |
● Resistance thermometer, relative to input range, (+/-) | Cuxxx Standard: ±0.3 K, Cuxxx Klima: ±0.2 K, Ptxxx Standard: ±0.5 K, Ptxxx Klima: ±0.2 K, Nixxx Standard: ±0.3 K, Nixxx Klima: ±0.15 K |
● Thermocouple, relative to input range, (+/-) | Type B: > 600 °C ±1 K, Type E: > -200 °C ±0.5 K, Type J: > -210 °C ±0.5 K, Type K: > -200 °C ±1 K, Type N: > -200 °C ±1 K, Type R: > 0 °C ±1 K, Type S: > 0 °C ±1 K, Type T: > -200 °C ±0.5 K, Type C: ±2 K, Type TXK/TXK(L): ±0.5 K |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | |
● Series mode interference (peak value of interference < rated value of input range), min. | 80 dB; in the Standard operating mode, 40 dB in the Fast operating mode |
● Common mode voltage, max. | 60 V DC/30 V AC |
● Common mode interference, min. | 80 dB |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Alarms | |
● Diagnostic alarm | Yes |
● Limit value alarm | Yes; two upper and two lower limit values in each case |
Diagnoses | |
● Monitoring the supply voltage | Yes |
● Wire-break | Yes; Only with TC, R, RTD |
● Overflow/underflow | Yes |
Diagnostics indication LED | |
● RUN LED | Yes; green LED |
● ERROR LED | Yes; red LED |
● Monitoring of the supply voltage (PWR-LED) | Yes; green LED |
● Channel status display | Yes; green LED |
● for channel diagnostics | Yes; red LED |
● for module diagnostics | Yes; red LED |
Potential separation | |
Potential separation channels | |
● between the channels | Yes |
● between the channels, in groups of | 1 |
● between the channels and backplane bus | Yes |
● between the channels and the power supply of the electronics | Yes |
Permissible potential difference | |
between different circuits | 60 V DC/30 V AC; insulation rated for 120 V AC basic insulation: between the channels and the supply voltage L+; between the channels and the backplane bus; between the channels |
Isolation | |
Isolation tested with | 2 000 V DC between the channels and the supply voltage L+; 2 000 V DC between the channels and the backplane bus; 2 000 V DC between the channels; 707 V DC (type test) between the supply voltage L+ and the backplane bus |
Standards, approvals, certificates | |
Suitable for applications according to AMS 2750 | Yes; Declaration of Conformity, see online support entry 109757262 |
Suitable for applications according to CQI-9 | Yes; Based on AMS 2750 E |
Ambient conditions | |
Ambient temperature during operation | |
● horizontal installation, min. | 0 °C |
● horizontal installation, max. | 60 °C |
● vertical installation, min. | 0 °C |
● vertical installation, max. | 40 °C |
Dimensions | |
Width | 35 mm |
Height | 147 mm |
Depth | 129 mm |
Weights | |
Weight, approx. | 290 g |
Other | |
Note: | for the R/RDT three-wire measurement, the conductor compensation is made alternating with the measurement; this then requires two module cycles for a measured value |
last modified: | 4/11/2022 |
Similar products:
Siemens S7-1500, AI 8xU/I HF; 6ES7531-7NF00-0AB0
SIMATIC S7-1500 analog input module AI 8xU/I HF, up to 24 bit resolution, accuracy 0.1%, 8 channels in groups of 1; common mode voltage: 30 V AC/60 V DC, Diagnostics;
-
(Out of stock)
Price on request
Siemens S7-1500, AI 8xU/I/R/RTD BA; 6ES7531-7QF00-0AB0
SIMATIC S7-1500 Analog input module, AI 8xU/I/R/RTD BA, 16 bit resolution, Accuracy 0.5%, 8 channels in groups of 8; Common mode voltage 4 V DC, Diagnostics; Hardware
-
(Out of stock)
Price on request
Siemens S7-1500, AI 16xU BA; 6ES7531-7LH00-0AB0
SIMATIC S7-1500, analog input module AI 16xU BA, 16-bit resolution accuracy 0.5%, 16 channels in groups of 16, common mode voltage 4 V DC, diagnostics, hardware
-
(Out of stock)
Price on request
Siemens S7-1500, AI 16xI BA; 6ES7531-7MH00-0AB0
SIMATIC S7-1500, analog input module AI 16xI BA, 16-bit resolution accuracy 0.5%, 16 channels in groups of 16, common mode voltage 4 V DC, diagnostics, hardware
-
(Out of stock)
Price on request
Siemens S7-1500, AI 8xU/I/RTD/TC ST; 6ES7531-7KF00-0AB0
SIMATIC S7-1500 analog input module AI 8xU/I/RTD/TC ST, 16 bit resolution, accuracy 0.3%, 8 channels in groups of 8; 4 channels for RTD measurement, common mode
-
(Out of stock)
Price on request
Siemens S7-1500, AI 8xU/I HS; 6ES7531-7NF10-0AB0
SIMATIC S7-1500 Analog input module AI 8xU/I HS, 16 bit resolution, Accuracy 0.3% 8 channels in groups of 8; Common mode voltage 10 V; Diagnostics; Hardware interrupts
-
(Out of stock)
Price on request