Siemens S7-1500, AI 8xU/I/R/RTD BA; 6ES7531-7QF00-0AB0
SIMATIC S7-1500 Analog input module, AI 8xU/I/R/RTD BA, 16 bit resolution, Accuracy 0.5%, 8 channels in groups of 8; Common mode voltage 4 V DC, Diagnostics; Hardware...
Price on request
SIMATIC S7-1500 Analog input module, AI 8xU/I/R/RTD BA, 16 bit resolution, Accuracy 0.5%, 8 channels in groups of 8; Common mode voltage 4 V DC, Diagnostics; Hardware interrupts; Delivery including infeed element, shield bracket and shield terminal: Front connector (screw terminals or push-in) to be ordered separately |
General information | |
Product type designation | AI 8xU/I/R/RTD BA |
HW functional status | FS01 |
Firmware version | V1.0.0 |
● FW update possible | Yes |
Product function | |
● I&M data | Yes; I&M0 to I&M3 |
● Prioritized startup | No |
Engineering with | |
● STEP 7 TIA Portal configurable/integrated from version | V15.1 / V16 |
● STEP 7 configurable/integrated from version | V5.5 SP3 / - |
● PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
● PROFINET from GSD version/GSD revision | V2.3 / - |
Operating mode | |
● Oversampling | No |
● MSI | Yes |
CiR - Configuration in RUN | |
Reparameterization possible in RUN | Yes |
Calibration possible in RUN | No |
Power | |
Power available from the backplane bus | 0.85 W |
Power loss | |
Power loss, typ. | 0.9 W |
Analog inputs | |
Number of analog inputs | 8 |
● For current measurement | 8 |
● For voltage measurement | 8 |
● For resistance/resistance thermometer measurement | 8 |
permissible input voltage for voltage input (destruction limit), max. | 12 V; 12 V continuous, 30 V for max. 1 s |
permissible input current for current input (destruction limit), max. | 40 mA |
Constant measurement current for resistance-type transmitter, typ. | 230 ... 370 µA |
Technical unit for temperature measurement adjustable | Yes; °C/°F/K |
Input ranges (rated values), voltages | |
● 0 to +5 V | No |
● 0 to +10 V | No |
● 1 V to 5 V | Yes |
— Input resistance (1 V to 5 V) | 10 MΩ |
● -1 V to +1 V | Yes |
— Input resistance (-1 V to +1 V) | 10 MΩ |
● -10 V to +10 V | Yes |
— Input resistance (-10 V to +10 V) | 10 MΩ |
● -2.5 V to +2.5 V | No |
● -25 mV to +25 mV | No |
● -250 mV to +250 mV | No |
● -5 V to +5 V | Yes |
— Input resistance (-5 V to +5 V) | 10 MΩ |
● -50 mV to +50 mV | Yes |
— Input resistance (-50 mV to +50 mV) | 10 MΩ |
● -500 mV to +500 mV | Yes |
— Input resistance (-500 mV to +500 mV) | 10 MΩ |
● -80 mV to +80 mV | No |
Input ranges (rated values), currents | |
● 0 to 20 mA | Yes |
— Input resistance (0 to 20 mA) | 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC |
● -20 mA to +20 mA | Yes |
— Input resistance (-20 mA to +20 mA) | 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC |
● 4 mA to 20 mA | Yes |
— Input resistance (4 mA to 20 mA) | 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC |
Input ranges (rated values), thermocouples | |
● Type B | No |
● Type C | No |
● Type E | No |
● Type J | No |
● Type K | No |
● Type L | No |
● Type N | No |
● Type R | No |
● Type S | No |
● Type T | No |
● Type U | No |
● Type TXK/TXK(L) to GOST | No |
Input ranges (rated values), resistance thermometer | |
● Cu 10 | No |
● Cu 10 according to GOST | No |
● Cu 50 | No |
● Cu 50 according to GOST | No |
● Cu 100 | No |
● Cu 100 according to GOST | No |
● Ni 10 | No |
● Ni 10 according to GOST | No |
● Ni 100 | Yes; Standard/climate |
— Input resistance (Ni 100) | 10 MΩ |
● Ni 100 according to GOST | No |
● Ni 1000 | Yes; Standard/climate |
— Input resistance (Ni 1000) | 10 MΩ |
● Ni 1000 according to GOST | No |
● LG-Ni 1000 | Yes; Standard/climate |
— Input resistance (LG-Ni 1000) | 10 MΩ |
● Ni 120 | No |
● Ni 120 according to GOST | No |
● Ni 200 | No |
● Ni 200 according to GOST | No |
● Ni 500 | No |
● Ni 500 according to GOST | No |
● Pt 10 | No |
● Pt 10 according to GOST | No |
● Pt 50 | No |
● Pt 50 according to GOST | No |
● Pt 100 | Yes; Standard/climate |
— Input resistance (Pt 100) | 10 MΩ |
● Pt 100 according to GOST | No |
● Pt 1000 | Yes; Standard/climate |
— Input resistance (Pt 1000) | 10 MΩ |
● Pt 1000 according to GOST | No |
● Pt 200 | No |
● Pt 200 according to GOST | No |
● Pt 500 | No |
● Pt 500 according to GOST | No |
Input ranges (rated values), resistors | |
● 0 to 150 ohms | No |
● 0 to 300 ohms | No |
● 0 to 600 ohms | Yes |
— Input resistance (0 to 600 ohms) | 10 MΩ |
● 0 to 3000 ohms | No |
● 0 to 6000 ohms | Yes |
— Input resistance (0 to 6000 ohms) | 10 MΩ |
● PTC | Yes |
— Input resistance (PTC) | 10 MΩ |
Cable length | |
● shielded, max. | 200 m; 50 m at 50 mV |
Analog value generation for the inputs | |
Measurement principle | integrating |
Integration and conversion time/resolution per channel | |
● Resolution with overrange (bit including sign), max. | 16 bit |
● Integration time, parameterizable | Yes |
● Integration time (ms) | 2,5 / 16,67 / 20 / 100 ms |
● Basic conversion time, including integration time (ms) | 10 / 24 / 27 / 107 ms |
— additional conversion time for wire-break monitoring | 4 ms (to be considered in R/RTD/U 1 to 5 V measurement) |
— additional conversion time for resistance measurement | 8 ms |
● Interference voltage suppression for interference frequency f1 in Hz | 400 / 60 / 50 / 10 Hz |
Smoothing of measured values | |
● parameterizable | Yes |
● Step: None | Yes |
● Step: low | Yes |
● Step: Medium | Yes |
● Step: High | Yes |
Encoder | |
Connection of signal encoders | |
● for voltage measurement | Yes |
● for current measurement as 2-wire transducer | Yes; with external supply |
● for current measurement as 4-wire transducer | Yes |
● for resistance measurement with two-wire connection | Yes; Only for PTC |
● for resistance measurement with three-wire connection | Yes; All measuring ranges except PTC; internal compensation of the cable resistances |
Errors/accuracies | |
Linearity error (relative to input range), (+/-) | 0.1 % |
Temperature error (relative to input range), (+/-) | 0.006 %/K |
Crosstalk between the inputs, max. | -50 dB |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.1 % |
Operational error limit in overall temperature range | |
● Voltage, relative to input range, (+/-) | 0.5 % |
● Current, relative to input range, (+/-) | 0.5 % |
● Resistance, relative to input range, (+/-) | 0.5 % |
● Resistance thermometer, relative to input range, (+/-) | Ptxxx Standard: ±1.2 K, Ptxxx Climate: ±0.8 K, Nixxx Standard: ±0.8 K, Nixxx Climate: ±0.8 K |
Basic error limit (operational limit at 25 °C) | |
● Voltage, relative to input range, (+/-) | 0.3 % |
● Current, relative to input range, (+/-) | 0.3 % |
● Resistance, relative to input range, (+/-) | 0.3 % |
● Resistance thermometer, relative to input range, (+/-) | Ptxxx Standard: ±1.0 K, Ptxxx Climate: ±0.5 K, Nixxx Standard: ±0.5 K, Nixxx Climate: ±0.5 K |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | |
● Series mode interference (peak value of interference < rated value of input range), min. | 40 dB |
● Common mode voltage, max. | 4 V |
● Common mode interference, min. | 60 dB |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Alarms | |
● Diagnostic alarm | Yes |
● Limit value alarm | Yes; two upper and two lower limit values in each case |
Diagnoses | |
● Monitoring the supply voltage | No |
● Wire-break | Yes; Only for 1 ... 5 V, 4 ... 20 mA, R, and RTD |
● Short-circuit | No |
● Group error | No |
● Overflow/underflow | Yes |
Diagnostics indication LED | |
● RUN LED | Yes; green LED |
● ERROR LED | Yes; red LED |
● MAINT LED | No |
● Monitoring of the supply voltage (PWR-LED) | No |
● Channel status display | Yes; green LED |
● for channel diagnostics | Yes; red LED |
● for module diagnostics | Yes; red LED |
Potential separation | |
Potential separation channels | |
● between the channels | No |
● between the channels, in groups of | 8 |
● between the channels and backplane bus | Yes |
Permissible potential difference | |
between the inputs (UCM) | 8 V DC |
Between the inputs and MANA (UCM) | 4 V DC |
Isolation | |
Isolation tested with | 707 V DC (type test) |
Ambient conditions | |
Ambient temperature during operation | |
● horizontal installation, min. | 0 °C |
● horizontal installation, max. | 60 °C |
● vertical installation, min. | 0 °C |
● vertical installation, max. | 40 °C |
Altitude during operation relating to sea level | |
● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
Dimensions | |
Width | 35 mm |
Height | 147 mm |
Depth | 129 mm |
Weights | |
Weight, approx. | 250 g |
last modified: | 1/19/2021 |
Similar products:
Siemens S7-1500, AI 8xU/I/RTD/TC ST; 6ES7531-7KF00-0AB0
SIMATIC S7-1500 analog input module AI 8xU/I/RTD/TC ST, 16 bit resolution, accuracy 0.3%, 8 channels in groups of 8; 4 channels for RTD measurement, common mode
-
(Out of stock)
Price on request
Siemens S7-1500, AI 8xU/I HS; 6ES7531-7NF10-0AB0
SIMATIC S7-1500 Analog input module AI 8xU/I HS, 16 bit resolution, Accuracy 0.3% 8 channels in groups of 8; Common mode voltage 10 V; Diagnostics; Hardware interrupts
-
(Out of stock)
Price on request
Siemens S7-1500, AI 8 X U/R/RTD/TC HF; 6ES7531-7PF00-0AB0
SIMATIC S7-1500 analog input module AI 8xU/R/RTD/TC HF, 16 bit resolution, up to 21 bit Resolution at RT and TC, accuracy 0.1%, 8 channels in groups of 1; common
-
(Out of stock)
Price on request
Siemens S7-1500, AI 8xU/I HF; 6ES7531-7NF00-0AB0
SIMATIC S7-1500 analog input module AI 8xU/I HF, up to 24 bit resolution, accuracy 0.1%, 8 channels in groups of 1; common mode voltage: 30 V AC/60 V DC, Diagnostics;
-
(Out of stock)
Price on request
Siemens S7-1500, AI 4xU/I/RTD/TC ST; 6ES7531-7QD00-0AB0
SIMATIC S7-1500 Analog input module AI 4xU/I/RTD/TC ST, 16 bit resolution, Accuracy 0.3%, 4 channels in groups of 4; 2 channels for RTD measurement; Common mode
-
(Out of stock)
Price on request
Siemens S7-1500, AI 16xU BA; 6ES7531-7LH00-0AB0
SIMATIC S7-1500, analog input module AI 16xU BA, 16-bit resolution accuracy 0.5%, 16 channels in groups of 16, common mode voltage 4 V DC, diagnostics, hardware
-
(Out of stock)
Price on request