Siemens S7-1500, AQ 4xU/I HF; 6ES7532-5ND00-0AB0
SIMATIC S7-1500, analog output module AQ 4xU/I HF, 16-bit resolution accuracy 0.1%, 4 channels in groups of 1, common mode voltage: 30 V AC/60 V DC, diagnostics;...
Price on request
SIMATIC S7-1500, analog output module AQ 4xU/I HF, 16-bit resolution accuracy 0.1%, 4 channels in groups of 1, common mode voltage: 30 V AC/60 V DC, diagnostics; substitute value, isochronous mode; the module supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015. delivery including infeed element, shielding bracket and shield terminal: front connector (screw terminals or push-in) to be ordered separately |
General information | |
Product type designation | AQ 4xU/I HF |
HW functional status | From FS01 |
Firmware version | V1.1.0 |
● FW update possible | Yes |
Product function | |
● I&M data | Yes; I&M0 to I&M3 |
● Isochronous mode | Yes |
● Prioritized startup | Yes |
Engineering with | |
● STEP 7 TIA Portal configurable/integrated from version | V14 / - |
● STEP 7 configurable/integrated from version | V5.5 SP3 / - |
● PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
● PROFINET from GSD version/GSD revision | V2.3 / - |
Operating mode | |
● Oversampling | No |
● MSO | Yes |
CiR - Configuration in RUN | |
Reparameterization possible in RUN | Yes |
Calibration possible in RUN | Yes |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current | |
Current consumption, max. | 160 mA |
Power | |
Power available from the backplane bus | 0.95 W |
Power loss | |
Power loss, typ. | 5 W |
Analog outputs | |
Number of analog outputs | 4 |
Voltage output, short-circuit protection | Yes |
Voltage output, short-circuit current, max. | 24 mA |
Current output, no-load voltage, max. | 22 V |
Cycle time (all channels), min. | 125 µs; independent of number of activated channels |
Output ranges, voltage | |
● 0 to 10 V | Yes |
● 1 V to 5 V | Yes |
● -5 V to +5 V | No |
● -10 V to +10 V | Yes |
Output ranges, current | |
● 0 to 20 mA | Yes |
● -20 mA to +20 mA | Yes |
● 4 mA to 20 mA | Yes |
Connection of actuators | |
● for voltage output two-wire connection | Yes |
● for voltage output four-wire connection | Yes |
● for current output two-wire connection | Yes |
Load impedance (in rated range of output) | |
● with voltage outputs, min. | 1 kΩ; 0.5 kOhm at 1 to 5 V |
● with voltage outputs, capacitive load, max. | 1 µF |
● with current outputs, max. | 750 Ω |
● with current outputs, inductive load, max. | 10 mH |
Cable length | |
● shielded, max. | 800 m; for current, 200 m for voltage |
Analog value generation for the outputs | |
Integration and conversion time/resolution per channel | |
● Resolution with overrange (bit including sign), max. | 16 bit |
● Conversion time (per channel) | 125 µs; independent of number of activated channels |
Settling time | |
● for resistive load | 0.2 ms; see additional description in the manual |
● for capacitive load | 1.8 ms; see additional description in the manual |
● for inductive load | 2 ms; see additional description in the manual |
Errors/accuracies | |
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) | 0.02 % |
Linearity error (relative to output range), (+/-) | 0.015 % |
Temperature error (relative to output range), (+/-) | 0.002 %/K |
Crosstalk between the outputs, max. | -100 dB |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.005 % |
note regarding accuracy | at temperatures below 0 °C, the figures for operating error and temperature error are doubled |
Operational error limit in overall temperature range | |
● Voltage, relative to output range, (+/-) | ±10 V; 0 V to 10 V: ±0.12%; 1 V to 5 V: ±0.1% |
● Current, relative to output range, (+/-) | ±20 mA; 0 mA to 20 mA: ±0.2%; 4 mA to 20 mA: ±0.12% |
Basic error limit (operational limit at 25 °C) | |
● Voltage, relative to output range, (+/-) | 0.06 % |
● Current, relative to output range, (+/-) | 0.1 % |
Isochronous mode | |
Execution and activation time (TCO), min. | 100 µs |
Bus cycle time (TDP), min. | 250 µs |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Substitute values connectable | Yes |
Alarms | |
● Diagnostic alarm | Yes |
Diagnoses | |
● Monitoring the supply voltage | Yes |
● Wire-break | Yes; Only for output type "current" |
● Short-circuit | Yes; Only for output type "voltage" |
● Overflow/underflow | Yes |
Diagnostics indication LED | |
● RUN LED | Yes; green LED |
● ERROR LED | Yes; red LED |
● Monitoring of the supply voltage (PWR-LED) | Yes; green LED |
● Channel status display | Yes; green LED |
● for channel diagnostics | Yes; red LED |
● for module diagnostics | Yes; red LED |
Potential separation | |
Potential separation channels | |
● between the channels | Yes |
● between the channels, in groups of | 1 |
● between the channels and backplane bus | Yes |
● Between the channels and load voltage L+ | Yes |
Permissible potential difference | |
between different circuits | 60 V DC/30 V AC; insulation rated for 120 V AC basic insulation: between the channels and the supply voltage L+; between the channels and the backplane bus; between the channels |
Isolation | |
Isolation tested with | 2 000 V DC between the channels and the supply voltage L+; 2 000 V DC between the channels and the backplane bus; 2 000 V DC between the channels; 707 V DC (type test) between the supply voltage L+ and the backplane bus |
Standards, approvals, certificates | |
Suitable for safety-related tripping of standard modules | Yes; From FS03 |
Highest safety class achievable for safety-related tripping of standard modules | |
● Performance level according to ISO 13849-1 | PL d |
● Category according to ISO 13849-1 | Cat. 3 |
● SIL acc. to IEC 62061 | SIL 2 |
● remark on safety-oriented shutdown | https://support.industry.siemens.com/cs/de/de/view/39198632 |
Ambient conditions | |
Ambient temperature during operation | |
● horizontal installation, min. | -25 °C; From FS02 |
● horizontal installation, max. | 60 °C |
● vertical installation, min. | -25 °C; From FS02 |
● vertical installation, max. | 40 °C |
Dimensions | |
Width | 35 mm |
Height | 147 mm |
Depth | 129 mm |
Weights | |
Weight, approx. | 300 g |
last modified: | 4/27/2022 |
Similar products:
Siemens S7-1500, AQ 2xU/I ST; 6ES7532-5NB00-0AB0
SIMATIC S7-1500, analog output module AQ 2x U/I ST, 16-bit resolution accuracy 0.3%. 2 channels in groups of 2, diagnostics; substitute value; the module supports
-
(Out of stock)
Price on request
Siemens S7-1500, AQ 8xU/I HS; 6ES7532-5HF00-0AB0
SIMATIC S7-1500, analog output module AQ8xU/I HS, 16-bit resolution accuracy 0.3%, 8 channels in groups of 8, diagnostics; substitute value 8 channels in 0.125 ms
-
(Out of stock)
Price on request
Siemens S7-1500, AQ 4xU/I ST; 6ES7532-5HD00-0AB0
SIMATIC S7-1500, analog output module AQ 4xU/I ST, 16-bit resolution accuracy 0.3%. 4 channels in groups of 4, diagnostics; substitute value; the module supports
-
(Out of stock)
Price on request
Siemens Universal Front Door IM155-5; 6ES7528-0AA70-7AA0
SIMATIC ET 200MP, spare part Front door for IM 155-5 (6ES7155-5AA00-0AB0) 5 units per packing unit
-
(Out of stock)
Price on request
Siemens SIMATIC S7-1500, Front connector in push-in design, 40-pole, for 35 mm wide modules; 6ES7592-1BM00-0XB0
SIMATIC S7-1500, Front connector in push-in design, 40-pole, for 35 mm wide modules incl. 4 potential bridges and cable ties
-
(Out of stock)
4.608,55