Siemens S7-1500, AQ 4xU/I ST; 6ES7532-5HD00-0AB0

Siemens S7-1500, AQ 4xU/I ST; 6ES7532-5HD00-0AB0

SIMATIC S7-1500, analog output module AQ 4xU/I ST, 16-bit resolution accuracy 0.3%. 4 channels in groups of 4, diagnostics; substitute value; the module supports...

Brand: Siemens
Product Code: 6ES7532-5HD00-0AB0
Availability: Check availability
Price on request
SIMATIC S7-1500, analog output module AQ 4xU/I ST, 16-bit resolution accuracy 0.3%. 4 channels in groups of 4, diagnostics; substitute value; the module supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 2 / PL c according to EN ISO 13849-1:2015. delivery including infeed element, shielding bracket and shield terminal: front connector (screw terminals or push-in) to be ordered separately

General information
Product type designation AQ 8xU/I HS
HW functional status From FS01
Firmware version V2.1.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode Yes
● Prioritized startup No
● Output range scalable No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V14 / -
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision V1.0 / V5.1
● PROFINET from GSD version/GSD revision V2.3 / -
Operating mode
● Oversampling Yes
● MSO Yes
CiR - Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 320 mA; with 19.2 V supply
Power
Power available from the backplane bus 1.15 W
Power loss
Power loss, typ. 7 W
Analog outputs
Number of analog outputs 8
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 45 mA
Current output, no-load voltage, max. 20 V
Cycle time (all channels), min. 125 µs; independent of number of activated channels
Output ranges, voltage
● 0 to 10 V Yes
● 1 V to 5 V Yes
● -5 V to +5 V No
● -10 V to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
Connection of actuators
● for voltage output two-wire connection Yes
● for voltage output four-wire connection Yes
● for current output two-wire connection Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 kΩ
● with voltage outputs, capacitive load, max. 100 nF
● with current outputs, max. 500 Ω
● with current outputs, inductive load, max. 1 mH
Cable length
● shielded, max. 200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Conversion time (per channel) 50 µs; independent of number of activated channels
Settling time
● for resistive load 30 µs; see additional description in the manual
● for capacitive load 100 µs; see additional description in the manual
● for inductive load 100 µs; see additional description in the manual
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) 0.02 %
Linearity error (relative to output range), (+/-) 0.15 %
Temperature error (relative to output range), (+/-) 0.002 %/K
Crosstalk between the outputs, max. -100 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) 0.05 %
note regarding accuracy at temperatures below 0 °C, the figures for operating error and temperature error are doubled
Operational error limit in overall temperature range
● Voltage, relative to output range, (+/-) 0.3 %
● Current, relative to output range, (+/-) 0.3 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output range, (+/-) 0.2 %
● Current, relative to output range, (+/-) 0.2 %
Isochronous mode
Execution and activation time (TCO), min. 100 µs
Bus cycle time (TDP), min. 250 µs
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Monitoring the supply voltage Yes
● Wire-break Yes; Only for output type "current"
● Short-circuit Yes; Only for output type "voltage"
● Overflow/underflow Yes
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● Monitoring of the supply voltage (PWR-LED) Yes; green LED
● Channel status display Yes; green LED
● for channel diagnostics Yes; red LED
● for module diagnostics Yes; red LED
Potential separation
Potential separation channels
● between the channels No
● between the channels, in groups of 8
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ Yes
Permissible potential difference
between S- and MANA (UCM) 8 V DC
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Suitable for safety-related tripping of standard modules Yes; from FS04
Highest safety class achievable for safety-related tripping of standard modules
● Performance level according to ISO 13849-1 PL d
● Category according to ISO 13849-1 Cat. 3
● SIL acc. to IEC 62061 SIL 2
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C; From FS03
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C; From FS03
● vertical installation, max. 40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width 35 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 325 g
last modified: 3/3/2022


Similar products:


Siemens S7-1500, AQ 8xU/I HS; 6ES7532-5HF00-0AB0

SIMATIC S7-1500, analog output module AQ8xU/I HS, 16-bit resolution accuracy 0.3%, 8 channels in groups of 8, diagnostics; substitute value 8 channels in 0.125 ms
-
Need to order

(Out of stock)

Price on request

Siemens S7-1500, AQ 4xU/I HF; 6ES7532-5ND00-0AB0

SIMATIC S7-1500, analog output module AQ 4xU/I HF, 16-bit resolution accuracy 0.1%, 4 channels in groups of 1, common mode voltage: 30 V AC/60 V DC, diagnostics;
-
Need to order

(Out of stock)

Price on request

Siemens S7-1500, AQ 2xU/I ST; 6ES7532-5NB00-0AB0

SIMATIC S7-1500, analog output module AQ 2x U/I ST, 16-bit resolution accuracy 0.3%. 2 channels in groups of 2, diagnostics; substitute value; the module supports
-
Need to order

(Out of stock)

Price on request

Siemens Universal Front Door S7-1500 IO (35mm); 6ES7528-0AA00-7AA0

SIMATIC S7-1500, spare part Front door for 35 mm width I/O modules; Consisting of: * Front door (unlasered), * Labeling strips (front) * Wiring diagram, 5 units
-
Need to order

(Out of stock)

Price on request

Siemens SIMATIC S7-1500, Front connector in push-in design, 40-pole, for 35 mm wide modules; 6ES7592-1BM00-0XB0

SIMATIC S7-1500, Front connector in push-in design, 40-pole, for 35 mm wide modules incl. 4 potential bridges and cable ties
-
Need to order

(Out of stock)

 
 
4.608,55

ELECTRO PNEUMATIC SOLUTIONS DOO

  • Jugoslovenska 2/13A, Čukarica, Beograd
  • Opening Times: Monday - Friday 8am-5pm
  • Telephone:
  • 011 257 1922
  • +381 64 659 66 55
  • +381 62 800 70 44
  • email: office@ep-solutions.rs

linkedin youtube instagram twitter facebook
1
2
3
Compare products Remove all products