Siemens S7-1500, AQ 8xU/I HS; 6ES7532-5HF00-0AB0
SIMATIC S7-1500, analog output module AQ8xU/I HS, 16-bit resolution accuracy 0.3%, 8 channels in groups of 8, diagnostics; substitute value 8 channels in 0.125 ms...
Price on request
SIMATIC S7-1500, analog output module AQ8xU/I HS, 16-bit resolution accuracy 0.3%, 8 channels in groups of 8, diagnostics; substitute value 8 channels in 0.125 ms oversampling; the module supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015. delivery including infeed element, shielding bracket and shield terminal: front connector (screw terminals or push-in) to be ordered separately |
General information | |
Product type designation | AQ 8xU/I HS |
HW functional status | From FS01 |
Firmware version | V2.1.0 |
● FW update possible | Yes |
Product function | |
● I&M data | Yes; I&M0 to I&M3 |
● Isochronous mode | Yes |
● Prioritized startup | No |
● Output range scalable | No |
Engineering with | |
● STEP 7 TIA Portal configurable/integrated from version | V14 / - |
● STEP 7 configurable/integrated from version | V5.5 SP3 / - |
● PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
● PROFINET from GSD version/GSD revision | V2.3 / - |
Operating mode | |
● Oversampling | Yes |
● MSO | Yes |
CiR - Configuration in RUN | |
Reparameterization possible in RUN | Yes |
Calibration possible in RUN | Yes |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current | |
Current consumption, max. | 320 mA; with 19.2 V supply |
Power | |
Power available from the backplane bus | 1.15 W |
Power loss | |
Power loss, typ. | 7 W |
Analog outputs | |
Number of analog outputs | 8 |
Voltage output, short-circuit protection | Yes |
Voltage output, short-circuit current, max. | 45 mA |
Current output, no-load voltage, max. | 20 V |
Cycle time (all channels), min. | 125 µs; independent of number of activated channels |
Output ranges, voltage | |
● 0 to 10 V | Yes |
● 1 V to 5 V | Yes |
● -5 V to +5 V | No |
● -10 V to +10 V | Yes |
Output ranges, current | |
● 0 to 20 mA | Yes |
● -20 mA to +20 mA | Yes |
● 4 mA to 20 mA | Yes |
Connection of actuators | |
● for voltage output two-wire connection | Yes |
● for voltage output four-wire connection | Yes |
● for current output two-wire connection | Yes |
Load impedance (in rated range of output) | |
● with voltage outputs, min. | 1 kΩ |
● with voltage outputs, capacitive load, max. | 100 nF |
● with current outputs, max. | 500 Ω |
● with current outputs, inductive load, max. | 1 mH |
Cable length | |
● shielded, max. | 200 m |
Analog value generation for the outputs | |
Integration and conversion time/resolution per channel | |
● Resolution with overrange (bit including sign), max. | 16 bit |
● Conversion time (per channel) | 50 µs; independent of number of activated channels |
Settling time | |
● for resistive load | 30 µs; see additional description in the manual |
● for capacitive load | 100 µs; see additional description in the manual |
● for inductive load | 100 µs; see additional description in the manual |
Errors/accuracies | |
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) | 0.02 % |
Linearity error (relative to output range), (+/-) | 0.15 % |
Temperature error (relative to output range), (+/-) | 0.002 %/K |
Crosstalk between the outputs, max. | -100 dB |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.05 % |
note regarding accuracy | at temperatures below 0 °C, the figures for operating error and temperature error are doubled |
Operational error limit in overall temperature range | |
● Voltage, relative to output range, (+/-) | 0.3 % |
● Current, relative to output range, (+/-) | 0.3 % |
Basic error limit (operational limit at 25 °C) | |
● Voltage, relative to output range, (+/-) | 0.2 % |
● Current, relative to output range, (+/-) | 0.2 % |
Isochronous mode | |
Execution and activation time (TCO), min. | 100 µs |
Bus cycle time (TDP), min. | 250 µs |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Substitute values connectable | Yes |
Alarms | |
● Diagnostic alarm | Yes |
Diagnoses | |
● Monitoring the supply voltage | Yes |
● Wire-break | Yes; Only for output type "current" |
● Short-circuit | Yes; Only for output type "voltage" |
● Overflow/underflow | Yes |
Diagnostics indication LED | |
● RUN LED | Yes; green LED |
● ERROR LED | Yes; red LED |
● Monitoring of the supply voltage (PWR-LED) | Yes; green LED |
● Channel status display | Yes; green LED |
● for channel diagnostics | Yes; red LED |
● for module diagnostics | Yes; red LED |
Potential separation | |
Potential separation channels | |
● between the channels | No |
● between the channels, in groups of | 8 |
● between the channels and backplane bus | Yes |
● Between the channels and load voltage L+ | Yes |
Permissible potential difference | |
between S- and MANA (UCM) | 8 V DC |
Isolation | |
Isolation tested with | 707 V DC (type test) |
Standards, approvals, certificates | |
Suitable for safety-related tripping of standard modules | Yes; from FS04 |
Highest safety class achievable for safety-related tripping of standard modules | |
● Performance level according to ISO 13849-1 | PL d |
● Category according to ISO 13849-1 | Cat. 3 |
● SIL acc. to IEC 62061 | SIL 2 |
Ambient conditions | |
Ambient temperature during operation | |
● horizontal installation, min. | -30 °C; From FS03 |
● horizontal installation, max. | 60 °C |
● vertical installation, min. | -30 °C; From FS03 |
● vertical installation, max. | 40 °C |
Altitude during operation relating to sea level | |
● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
Dimensions | |
Width | 35 mm |
Height | 147 mm |
Depth | 129 mm |
Weights | |
Weight, approx. | 325 g |
last modified: | 3/3/2022 |
Similar products:
Siemens S7-1500, AQ 4xU/I ST; 6ES7532-5HD00-0AB0
SIMATIC S7-1500, analog output module AQ 4xU/I ST, 16-bit resolution accuracy 0.3%. 4 channels in groups of 4, diagnostics; substitute value; the module supports
-
(Out of stock)
Price on request
Siemens S7-1500, AQ 4xU/I HF; 6ES7532-5ND00-0AB0
SIMATIC S7-1500, analog output module AQ 4xU/I HF, 16-bit resolution accuracy 0.1%, 4 channels in groups of 1, common mode voltage: 30 V AC/60 V DC, diagnostics;
-
(Out of stock)
Price on request
Siemens S7-1500, AQ 2xU/I ST; 6ES7532-5NB00-0AB0
SIMATIC S7-1500, analog output module AQ 2x U/I ST, 16-bit resolution accuracy 0.3%. 2 channels in groups of 2, diagnostics; substitute value; the module supports
-
(Out of stock)
Price on request
Siemens S7-1500, DQ 8x230VAC/5A ST (Relay); 6ES7522-5HF00-0AB0
SIMATIC S7-1500, digital output module DQ 8xAC 230V/5A ST; relay; 8 channels in groups of 1; 5 A per group; diagnostics; substitute value: switching cycle counter
-
(Out of stock)
Price on request
Siemens SIMATIC S7-1500, Front connector in push-in design, 40-pole, for 35 mm wide modules; 6ES7592-1BM00-0XB0
SIMATIC S7-1500, Front connector in push-in design, 40-pole, for 35 mm wide modules incl. 4 potential bridges and cable ties
-
(Out of stock)
4.608,55