Siemens S7-1500, DI 32x24VDC/DQ 32x24VDC/0.3A BA; 6ES7523-1BP50-0AA0
SIMATIC S7-1500 digital input/output module, DI 32x24VDC BA SNK / SRC, 32 channels in groups of 16, input delay typ. 3.2 ms input type 3 (IEC 61131), sinking/sourcing...
Price on request
SIMATIC S7-1500 digital input/output module, DI 32x24VDC BA SNK / SRC, 32 channels in groups of 16, input delay typ. 3.2 ms input type 3 (IEC 61131), sinking/sourcing input, DQ 32XDC 24V/0.3A SNK BA; 32 channels in groups of 16; 2 A per group at 60 °C; sourcing output; 35 mm wide; cables and terminal blocks to be ordered separately as accessories |
General information | |
Product type designation | DI 32 x 24 V DC / DQ 32 x 24 V DC/0.3A SNK BA |
HW functional status | From FS01 |
Firmware version | V1.0.0 |
● FW update possible | Yes |
Product function | |
● I&M data | Yes; I&M0 to I&M3 |
● Isochronous mode | No |
● Prioritized startup | No |
Engineering with | |
● STEP 7 TIA Portal configurable/integrated from version | V16 with HSP 0319 / V17 |
● STEP 7 configurable/integrated from version | V5.5 SP3 / - |
● PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
● PROFINET from GSD version/GSD revision | V2.35 / - |
Operating mode | |
● DI | Yes |
● Counter | No |
● DQ | Yes |
● DQ with energy-saving function | No |
● PWM | No |
● Cam control (switching at comparison values) | No |
● Oversampling | No |
● MSI | Yes |
● MSO | Yes |
● Integrated operating cycle counter | No |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes; Through internal protection with 4 A per group |
external protection for power supply lines (recommendation) | input side: 24 V DC/4 A miniature circuit breaker with type B or C tripping characteristic; output side: 24 V DC/6 A miniature circuit breaker with type B tripping characteristic |
Input current | |
Current consumption, max. | 45 mA; without load |
output voltage / header | |
Rated value (DC) | 24 V |
Power | |
Power available from the backplane bus | 0.6 W |
Power loss | |
Power loss, typ. | 4.7 W |
Digital inputs | |
Number of digital inputs | 32 |
Digital inputs, parameterizable | No |
Source/sink input | Yes |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
Number of simultaneously controllable inputs | |
● Number of simultaneously controllable inputs | 32 |
horizontal installation | |
— up to 60 °C, max. | 32 |
vertical installation | |
— up to 40 °C, max. | 16 |
Input voltage | |
● Rated value (DC) | 24 V |
● for signal "0" | -5 ... +5 V (reference potential is COM) |
● for signal "1" | -11 ... -30 V; +11 ... +30 V (reference potential is COM) |
Input current | |
● for signal "1", typ. | 2.7 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
— parameterizable | No |
— at "0" to "1", min. | 3 ms |
— at "0" to "1", max. | 4 ms |
— at "1" to "0", min. | 3 ms |
— at "1" to "0", max. | 4 ms |
for interrupt inputs | |
— parameterizable | No |
for technological functions | |
— parameterizable | No |
Cable length | |
● shielded, max. | 1 000 m |
● unshielded, max. | 600 m |
Digital outputs | |
Type of digital output | Transistor |
Number of digital outputs | 32 |
Current-sinking | Yes |
Current-sourcing | No |
Digital outputs, parameterizable | No |
Short-circuit protection | No; external fusing necessary, max. 4 A per group, tripping characteristic type B or C |
Limitation of inductive shutdown voltage to | L+ (-53 V) |
Controlling a digital input | Yes |
Switching capacity of the outputs | |
● with resistive load, max. | 0.3 A |
● on lamp load, max. | 5 W |
Load resistance range | |
● lower limit | 80 Ω |
● upper limit | 10 kΩ |
Output voltage | |
● for signal "1", min. | M+ (0.5 V) |
Output current | |
● for signal "1" rated value | 0.3 A |
● for signal "1" permissible range, max. | 0.3 A |
● for signal "0" residual current, max. | 0.5 mA |
Output delay with resistive load | |
● "0" to "1", max. | 100 µs |
● "1" to "0", max. | 500 µs |
Parallel switching of two outputs | |
● for logic links | Yes |
● for uprating | No |
● for redundant control of a load | Yes |
Switching frequency | |
● with resistive load, max. | 100 Hz |
● with inductive load, max. | 0.5 Hz; According to IEC 60947-5-1, DC-13 |
● on lamp load, max. | 10 Hz |
Total current of the outputs | |
● Current per channel, max. | 0.3 A |
● Current per group, max. | 2 A |
● Current per module, max. | 4 A |
Total current of the outputs (per module) | |
horizontal installation | |
— up to 60 °C, max. | 4 A |
vertical installation | |
— up to 40 °C, max. | 4 A |
Cable length | |
● shielded, max. | 1 000 m |
● unshielded, max. | 600 m |
Encoder | |
Connectable encoders | |
● 2-wire sensor | Yes |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA |
Interrupts/diagnostics/status information | |
Diagnostics function | No |
Substitute values connectable | No |
Alarms | |
● Diagnostic alarm | No |
● Maintenance interrupt | No |
● Hardware interrupt | No |
Diagnoses | |
● Monitoring the supply voltage | No |
● Wire-break | No |
● Short-circuit | No |
● Group error | No |
Diagnostics indication LED | |
● RUN LED | Yes; green LED |
● ERROR LED | Yes; red LED |
● MAINT LED | No |
● Monitoring of the supply voltage (PWR-LED) | Yes; via SIMATIC TOP connect connection module |
● Channel status display | Yes; via SIMATIC TOP connect connection module |
● for channel diagnostics | No |
● for module diagnostics | No |
Potential separation | |
Potential separation channels | |
● between the channels | No |
● between the channels, in groups of | 16; 32 when using SIMATIC TOP connect connection module |
● between the channels and backplane bus | Yes |
Isolation | |
Isolation tested with | 707 V DC (type test) |
Ambient conditions | |
Ambient temperature during operation | |
● horizontal installation, min. | -30 °C |
● horizontal installation, max. | 60 °C |
● vertical installation, min. | -30 °C |
● vertical installation, max. | 40 °C |
Altitude during operation relating to sea level | |
● Installation altitude above sea level, max. | 5 000 m |
Dimensions | |
Width | 35 mm |
Height | 147 mm |
Depth | 129 mm |
Weights | |
Weight, approx. | 250 g |
Other | |
Note: | Please order cable and connection modules separately |
last modified: | 1/16/2021 |
Similar products:
Siemens S7-1500, DI 16x24VDC/DQ 16x24VDC/0.5A BA; 6ES7523-1BL00-0AA0
SIMATIC S7-1500 digital input/output module, DI16x 24VDC BA, 16 channels in groups of 16, input delay typ. 3.2 ms input type 3 (IEC 61131), DQ16XDC 24V/0.5A BA;
-
(Out of stock)
Price on request
Siemens S7-1500, AI 4xU/I/RTD/TC ST; 6ES7531-7QD00-0AB0
SIMATIC S7-1500 Analog input module AI 4xU/I/RTD/TC ST, 16 bit resolution, Accuracy 0.3%, 4 channels in groups of 4; 2 channels for RTD measurement; Common mode
-
(Out of stock)
Price on request
Siemens S7-1500, DQ 64x24VDC/0.3A BA; 6ES7522-1BP00-0AA0
SIMATIC S7-1500, digital output module, DQ 64xDC 24V/0,3A BA, 64 channels in groups of 16, 2 A per group at 60 °C, sinking output, 35 mm wide, the module supports
-
(Out of stock)
Price on request
Siemens SIMATIC S7-1500, Front connector in push-in design, 40-pole, for 35 mm wide modules; 6ES7592-1BM00-0XB0
SIMATIC S7-1500, Front connector in push-in design, 40-pole, for 35 mm wide modules incl. 4 potential bridges and cable ties
-
(Out of stock)
4.608,55