Siemens S7-1500, DQ 16x24...48VUC/125VDC/0.5A ST; 6ES7522-5EH00-0AB0
SIMATIC S7-1500, digital output module DQ16x24..48VUC/125V DC/0.5A ST; 16 channels in groups of 1; 0.5 A per group; substitute value: observe derating the module...
Price on request
SIMATIC S7-1500, digital output module DQ16x24..48VUC/125V DC/0.5A ST; 16 channels in groups of 1; 0.5 A per group; substitute value: observe derating the module supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015. front connector (screw terminals or push-in) to be ordered separately |
General information | |
Product type designation | DQ 16x24 ... 48 V UC/125 V DC/0.5 A ST |
HW functional status | FS02 |
Firmware version | V1.0.0 |
● FW update possible | Yes |
Product function | |
● I&M data | Yes; I&M0 to I&M3 |
● Isochronous mode | No |
● Prioritized startup | Yes |
Engineering with | |
● STEP 7 TIA Portal configurable/integrated from version | V13 SP1 / - |
● STEP 7 configurable/integrated from version | V5.5 SP3 / - |
● PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
● PROFINET from GSD version/GSD revision | V2.3 / - |
Operating mode | |
● DQ | Yes |
● DQ with energy-saving function | No |
● PWM | No |
● Cam control (switching at comparison values) | No |
● Oversampling | No |
● MSO | Yes |
● Integrated operating cycle counter | No |
output voltage / header | |
Rated value (DC) | 24 V; 48 V, 125 V |
Rated value (AC) | 24 V; 48 V (50 - 60 Hz) |
Power | |
Power available from the backplane bus | 2 W |
Power loss | |
Power loss, typ. | 3.8 W |
Digital outputs | |
Type of digital output | Transistor |
Number of digital outputs | 16 |
Current-sinking | Yes |
Current-sourcing | Yes |
Digital outputs, parameterizable | Yes |
Limitation of inductive shutdown voltage to | 200 V (suppressor diode) |
Controlling a digital input | Yes |
Switching capacity of the outputs | |
● with resistive load, max. | 0.5 A |
● on lamp load, max. | 40 W; At 125 V DC, 10 W at 48 V UC, 5 W at 24 V UC |
Output voltage | |
● for signal "1", min. | L+ (-1.0 V) |
Output current | |
● for signal "1" rated value | 0.5 A |
● for signal "1" permissible range, max. | 0.6 A |
Output delay with resistive load | |
● "0" to "1", max. | 5 ms |
● "1" to "0", max. | 5 ms |
Parallel switching of two outputs | |
● for logic links | Yes |
● for uprating | No |
● for redundant control of a load | Yes |
Switching frequency | |
● with resistive load, max. | 25 Hz |
● with inductive load, max. | 0.5 Hz |
● on lamp load, max. | 10 Hz |
Total current of the outputs | |
● Current per channel, max. | 0.5 A |
● Current per group, max. | 0.5 A |
● Current per module, max. | 8 A |
Cable length | |
● shielded, max. | 1 000 m |
● unshielded, max. | 600 m |
Interrupts/diagnostics/status information | |
Diagnostics function | No |
Substitute values connectable | Yes |
Alarms | |
● Diagnostic alarm | No |
● Maintenance interrupt | No |
Diagnoses | |
● Monitoring the supply voltage | No |
● Wire-break | No |
● Short-circuit | No |
Diagnostics indication LED | |
● RUN LED | Yes; green LED |
● ERROR LED | Yes; red LED |
● Monitoring of the supply voltage (PWR-LED) | No |
● Channel status display | Yes; green LED |
● for channel diagnostics | No |
● for module diagnostics | Yes; red LED |
Potential separation | |
Potential separation channels | |
● between the channels | Yes |
● between the channels, in groups of | 1 |
● between the channels and backplane bus | Yes |
Permissible potential difference | |
between different circuits | 125 V DC/48 V AC |
Isolation | |
Isolation tested with | 2 000 V DC |
Standards, approvals, certificates | |
Suitable for safety functions | No |
Suitable for safety-related tripping of standard modules | Yes; From FS02 |
Highest safety class achievable for safety-related tripping of standard modules | |
● Performance level according to ISO 13849-1 | PL d |
● Category according to ISO 13849-1 | Cat. 3 |
● SIL acc. to IEC 62061 | SIL 2 |
Ambient conditions | |
Ambient temperature during operation | |
● horizontal installation, min. | 0 °C |
● horizontal installation, max. | 60 °C |
● vertical installation, min. | 0 °C |
● vertical installation, max. | 40 °C |
Dimensions | |
Width | 35 mm |
Height | 147 mm |
Depth | 129 mm |
Weights | |
Weight, approx. | 230 g |
last modified: | 3/3/2022 |
Similar products:
Siemens S7-1500, DQ 32x24VDC/0.5A BA; 6ES7522-1BL10-0AA0
SIMATIC S7-1500, digital output module, DQ32xDC 24V/0.5A BA, 32 channels in groups of 8, 4 A per group; the module supports the safety-oriented shutdown of load
-
(Out of stock)
Price on request
Siemens S7-1500, DQ 16x24V DC/0.5A HF; 6ES7522-1BH01-0AB0
SIMATIC S7-1500, digital output module DQ16x24 V DC/0.5A HF; 16 channels in groups of 8; 4 A per group; single-channel diagnostics; substitute value: switching cycle
-
(Out of stock)
Price on request
Siemens S7-1500, DQ 16x24VDC/0.5A BA; 6ES7522-1BH10-0AA0
SIMATIC S7-1500, digital output module, DQ16xDC 24V/0.5A BA, 16 channels in groups of 8, 4 A per group; the module supports the safety-oriented shutdown of load
-
(Out of stock)
Price on request
Siemens S7-1500, DQ 8x24VDC/2A HF; 6ES7522-1BF00-0AB0
SIMATIC S7-1500, digital output module DQ 8x24 V DC/2A HF; 8 channels in groups of 8; 8 A per group; diagnostics; substitute value: 2 channels can be used for pulse
-
(Out of stock)
Price on request
Siemens S7-1500, DQ 8x230VAC/2A ST (Triac); 6ES7522-5FF00-0AB0
SIMATIC S7-1500, digital output module DQ 8x230 V AC/2 A ST; TRIAC; 8 channels in groups of 1; 2 A per group; Substitute value: Front connector (screw terminals
-
(Out of stock)
Price on request
Siemens S7-1500, DQ 8x230VAC/5A ST (Relay); 6ES7522-5HF00-0AB0
SIMATIC S7-1500, digital output module DQ 8xAC 230V/5A ST; relay; 8 channels in groups of 1; 5 A per group; diagnostics; substitute value: switching cycle counter
-
(Out of stock)
Price on request