Siemens CPU 1515-2 PN, 500KB Prog., 3MB Data; 6ES7515-2AM02-0AB0
SIMATIC S7-1500, CPU 1515-2 PN, central processing unit with 500 KB work memory for program and 3 MB for data, 1st interface: PROFINET IRT with 2-port switch, 2nd...
Cena bez pdv-a: 297.696,92 |
Cena sa pdv-om: 357.236,30 |
SIMATIC S7-1500, CPU 1515-2 PN, central processing unit with 500 KB work memory for program and 3 MB for data, 1st interface: PROFINET IRT with 2-port switch, 2nd interface: PROFINET RT, 30 ns bit performance, SIMATIC Memory Card required
General information |
|
Product type designation | CPU 1515-2 PN |
HW functional status | FS01 |
Firmware version | V2.9 |
Product function | |
● I&M data | Yes; I&M0 to I&M3 |
● Isochronous mode | Yes; Distributed and central; with minimum OB 6x cycle of 500 µs (distributed) and 1 ms (central) |
Engineering with | |
● STEP 7 TIA Portal configurable/integrated from version | V17 (FW V2.9) / V16 (FW V2.8) or higher; with older TIA Portal versions configurable as 6ES7515-2AM01-0AB0 |
Configuration control | |
via dataset | Yes |
Display | |
Screen diagonal [cm] | 6.1 cm |
Control elements | |
Number of keys | 8 |
Mode buttons | 2 |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Mains buffering | |
● Mains/voltage failure stored energy time | 5 ms |
● Repeat rate, min. | 1/s |
Input current | |
Current consumption (rated value) | 0.8 A |
Current consumption, max. | 1.1 A |
Inrush current, max. | 2.4 A; Rated value |
I²t | 0.02 A²·s |
Power | |
Infeed power to the backplane bus | 12 W |
Power consumption from the backplane bus (balanced) | 6.2 W |
Power loss | |
Power loss, typ. | 6.3 W |
Memory | |
Number of slots for SIMATIC memory card | 1 |
SIMATIC memory card required | Yes |
Work memory | |
● integrated (for program) | 500 kbyte |
● integrated (for data) | 3 Mbyte |
Load memory | |
● Plug-in (SIMATIC Memory Card), max. | 32 Gbyte |
Backup | |
● maintenance-free | Yes |
CPU processing times | |
for bit operations, typ. | 30 ns |
for word operations, typ. | 36 ns |
for fixed point arithmetic, typ. | 48 ns |
for floating point arithmetic, typ. | 192 ns |
CPU-blocks | |
Number of elements (total) | 8 000; Blocks (OB, FB, FC, DB) and UDTs |
DB | |
● Number range | 1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999 |
● Size, max. | 3 Mbyte; For DBs with absolute addressing, the max. size is 64 KB |
FB | |
● Number range | 0 ... 65 535 |
● Size, max. | 500 kbyte |
FC | |
● Number range | 0 ... 65 535 |
● Size, max. | 500 kbyte |
OB | |
● Size, max. | 500 kbyte |
● Number of free cycle OBs | 100 |
● Number of time alarm OBs | 20 |
● Number of delay alarm OBs | 20 |
● Number of cyclic interrupt OBs | 20; With minimum OB 3x cycle of 500 µs |
● Number of process alarm OBs | 50 |
● Number of DPV1 alarm OBs | 3 |
● Number of isochronous mode OBs | 2 |
● Number of technology synchronous alarm OBs | 2 |
● Number of startup OBs | 100 |
● Number of asynchronous error OBs | 4 |
● Number of synchronous error OBs | 2 |
● Number of diagnostic alarm OBs | 1 |
Nesting depth | |
● per priority class | 24 |
Counters, timers and their retentivity | |
S7 counter | |
● Number | 2 048 |
Retentivity | |
— adjustable | Yes |
IEC counter | |
● Number | Any (only limited by the main memory) |
Retentivity | |
— adjustable | Yes |
S7 times | |
● Number | 2 048 |
Retentivity | |
— adjustable | Yes |
IEC timer | |
● Number | Any (only limited by the main memory) |
Retentivity | |
— adjustable | Yes |
Data areas and their retentivity | |
Retentive data area (incl. timers, counters, flags), max. | 512 kbyte; In total; available retentive memory for bit memories, timers, counters, DBs, and technology data (axes): 472 KB |
Extended retentive data area (incl. timers, counters, flags), max. | 3 Mbyte; When using PS 6 0W 24/48/60 V DC HF |
Flag | |
● Size, max. | 16 kbyte |
● Number of clock memories | 8; 8 clock memory bit, grouped into one clock memory byte |
Data blocks | |
● Retentivity adjustable | Yes |
● Retentivity preset | No |
Local data | |
● per priority class, max. | 64 kbyte; max. 16 KB per block |
Address area | |
Number of IO modules | 8 192; max. number of modules / submodules |
I/O address area | |
● Inputs | 32 kbyte; All inputs are in the process image |
● Outputs | 32 kbyte; All outputs are in the process image |
per integrated IO subsystem | |
— Inputs (volume) | 8 kbyte |
— Outputs (volume) | 8 kbyte |
per CM/CP | |
— Inputs (volume) | 8 kbyte |
— Outputs (volume) | 8 kbyte |
Subprocess images | |
● Number of subprocess images, max. | 32 |
Hardware configuration | |
Number of distributed IO systems | 64; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET or PROFIBUS communication modules, but also by the connection of I/O via AS-i master modules or links (e.g. IE/PB-Link) |
Number of DP masters | |
● Via CM | 8; A maximum of 8 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total |
Number of IO Controllers | |
● integrated | 2 |
● Via CM | 8; A maximum of 8 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total |
Rack | |
● Modules per rack, max. | 32; CPU + 31 modules |
● Number of lines, max. | 1 |
PtP CM | |
● Number of PtP CMs | the number of connectable PtP CMs is only limited by the number of available slots |
Time of day | |
Clock | |
● Type | Hardware clock |
● Backup time | 6 wk; At 40 °C ambient temperature, typically |
● Deviation per day, max. | 10 s; Typ.: 2 s |
Operating hours counter | |
● Number | 16 |
Clock synchronization | |
● supported | Yes |
● in AS, master | Yes |
● in AS, slave | Yes |
● on Ethernet via NTP | Yes |
Interfaces | |
Number of PROFINET interfaces | 2 |
1. Interface | |
Interface types | |
● RJ 45 (Ethernet) | Yes; X1 |
● Number of ports | 2 |
● integrated switch | Yes |
Protocols | |
● IP protocol | Yes; IPv4 |
● PROFINET IO Controller | Yes |
● PROFINET IO Device | Yes |
● SIMATIC communication | Yes |
● Open IE communication | Yes; Optionally also encrypted |
● Web server | Yes |
● Media redundancy | Yes |
PROFINET IO Controller | |
Services | |
— PG/OP communication | Yes |
— Isochronous mode | Yes |
— Direct data exchange | Yes; Requirement: IRT and isochronous mode (MRPD optional) |
— IRT | Yes |
— PROFIenergy | Yes; per user program |
— Prioritized startup | Yes; Max. 32 PROFINET devices |
— Number of connectable IO Devices, max. | 256; In total, up to 1 000 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET |
— Of which IO devices with IRT, max. | 64 |
— Number of connectable IO Devices for RT, max. | 256 |
— of which in line, max. | 256 |
— Number of IO Devices that can be simultaneously activated/deactivated, max. | 8; in total across all interfaces |
— Number of IO Devices per tool, max. | 8 |
— Updating times | The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data |
Update time for IRT | |
— for send cycle of 250 µs | 250 μs to 4 ms; Note: In the case of IRT with isochronous mode, the minimum update time of 500 µs of the isochronous OB is decisive |
— for send cycle of 500 µs | 500 µs to 8 ms |
— for send cycle of 1 ms | 1 ms to 16 ms |
— for send cycle of 2 ms | 2 ms to 32 ms |
— for send cycle of 4 ms | 4 ms to 64 ms |
— With IRT and parameterization of "odd" send cycles | Update time = set "odd" send clock (any multiple of 125 µs: 375 µs, 625 µs ... 3 875 µs) |
Update time for RT | |
— for send cycle of 250 µs | 250 µs to 128 ms |
— for send cycle of 500 µs | 500 µs to 256 ms |
— for send cycle of 1 ms | 1 ms to 512 ms |
— for send cycle of 2 ms | 2 ms to 512 ms |
— for send cycle of 4 ms | 4 ms to 512 ms |
PROFINET IO Device | |
Services | |
— PG/OP communication | Yes |
— Isochronous mode | No |
— IRT | Yes |
— PROFIenergy | Yes; per user program |
— Shared device | Yes |
— Number of IO Controllers with shared device, max. | 4 |
— activation/deactivation of I-devices | Yes; per user program |
— Asset management record | Yes; per user program |
2. Interface | |
Interface types | |
● RJ 45 (Ethernet) | Yes; X2 |
● Number of ports | 1 |
● integrated switch | No |
Protocols | |
● IP protocol | Yes; IPv4 |
● PROFINET IO Controller | Yes |
● PROFINET IO Device | Yes |
● SIMATIC communication | Yes |
● Open IE communication | Yes; Optionally also encrypted |
● Web server | Yes |
● Media redundancy | No |
PROFINET IO Controller | |
Services | |
— PG/OP communication | Yes |
— Isochronous mode | No |
— Direct data exchange | No |
— IRT | No |
— PROFIenergy | Yes; per user program |
— Prioritized startup | No |
— Number of connectable IO Devices, max. | 32; In total, up to 1 000 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET |
— Number of connectable IO Devices for RT, max. | 32 |
— of which in line, max. | 32 |
— Number of IO Devices that can be simultaneously activated/deactivated, max. | 8; in total across all interfaces |
— Number of IO Devices per tool, max. | 8 |
— Updating times | The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data |
Update time for RT | |
— for send cycle of 1 ms | 1 ms to 512 ms |
PROFINET IO Device | |
Services | |
— PG/OP communication | Yes |
— Isochronous mode | No |
— IRT | No |
— PROFIenergy | Yes; per user program |
— Prioritized startup | No |
— Shared device | Yes |
— Number of IO Controllers with shared device, max. | 4 |
— activation/deactivation of I-devices | Yes; per user program |
— Asset management record | Yes; per user program |
Interface types | |
RJ 45 (Ethernet) | |
● 100 Mbps | Yes |
● Autonegotiation | Yes |
● Autocrossing | Yes |
● Industrial Ethernet status LED | Yes |
Protocols | |
PROFIsafe | No |
Number of connections | |
● Number of connections, max. | 192; via integrated interfaces of the CPU and connected CPs / CMs |
● Number of connections reserved for ES/HMI/web | 10 |
● Number of connections via integrated interfaces | 108 |
● Number of S7 routing paths | 16 |
Redundancy mode | |
● H-Sync forwarding | Yes |
Media redundancy | |
— Media redundancy | only via 1st interface (X1) |
— MRP | Yes; MRP Automanager according to IEC 62439-2 Edition 2.0, MRP Manager; MRP Client |
— MRP interconnection, supported | Yes; as MRP ring node according to IEC 62439-2 Edition 3.0 |
— MRPD | Yes; Requirement: IRT |
— Switchover time on line break, typ. | 200 ms; For MRP, bumpless for MRPD |
— Number of stations in the ring, max. | 50 |
SIMATIC communication | |
● PG/OP communication | Yes; encryption with TLS V1.3 pre-selected |
● S7 routing | Yes |
● S7 communication, as server | Yes |
● S7 communication, as client | Yes |
● User data per job, max. | See online help (S7 communication, user data size) |
Open IE communication | |
● TCP/IP | Yes |
— Data length, max. | 64 kbyte |
— several passive connections per port, supported | Yes |
● ISO-on-TCP (RFC1006) | Yes |
— Data length, max. | 64 kbyte |
● UDP | Yes |
— Data length, max. | 2 kbyte; 1 472 bytes for UDP broadcast |
— UDP multicast | Yes; Max. 5 multicast circuits |
● DHCP | Yes |
● DNS | Yes |
● SNMP | Yes |
● DCP | Yes |
● LLDP | Yes |
● Encryption | Yes; Optional |
Web server | |
● HTTP | Yes; Standard and user pages |
● HTTPS | Yes; Standard and user pages |
OPC UA | |
● Runtime license required | Yes; "Medium" license |
Slicni proizvodi:
Siemens SIMATIC S7-1500 Compact CPU CPU 1511C-1PN, central processing unit with working memory 175 KB for program and 1 MB for data; 6ES
SIMATIC S7-1500 Compact CPU CPU 1511C-1PN, central processing unit with working memory 175 KB for program and 1 MB for data, 16 digital inputs, 16 digital outputs,
-
(Trenutno nema na stanju)
Cena na upit
Siemens SIMATIC S7-1500 Compact CPU CPU 1512C-1 PN, central processing unit with working memory 250 KB for program and 1 MB for data; 6E
SIMATIC S7-1500 Compact CPU CPU 1512C-1 PN, central processing unit with working memory 250 KB for program and 1 MB for data, 32 digital inputs, 32 digital outputs,
-
(Trenutno nema na stanju)
Cena na upit
Siemens CPU 1518F-4 PN/DP, 9 MB Prog, 60MB Data; 6ES7518-4FP00-0AB0
SIMATIC S7-1500F, CPU 1518F-4 PN/DP, central processing unit with 9 MB work memory for program and 60 MB for data, 1st interface: PROFINET IRT with 2-port switch,
-
(Trenutno nema na stanju)
Cena na upit
Siemens CPU 1518-4 PN/DP MFP + C/C++ RT + OPC UA; 6ES7518-4AX00-1AC0
SIMATIC S7-1500, CPU Bundle consisting of: CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0), including C/C++ Runtime and OPC UA Runtime license, 6 MB work memory for program
-
(Trenutno nema na stanju)
Cena na upit
Siemens CPU 1518F-4 PN/DP MFP + C/C++ RT +OPC UA; 6ES7518-4FX00-1AC0
SIMATIC S7-1500F, CPU Bundle consisting of: CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0), including C/C++ Runtime and OPC UA Runtime license, 9 MB work memory for
-
(Trenutno nema na stanju)
Cena na upit
Siemens CPU 1518-4 PN/DP, 6 MB Prog., 60MB Data; 6ES7518-4AP00-0AB0
SIMATIC S7-1500, CPU 1518-4 PN/DP, central processing unit with 6 MB work memory for program and 60 MB for data, 1st interface: PROFINET IRT with 2-port switch,
-
(Trenutno nema na stanju)
950.816,34