Siemens S7-1500, DQ 8x230VAC/5A ST (Relay); 6ES7522-5HF00-0AB0
SIMATIC S7-1500, digital output module DQ 8xAC 230V/5A ST; relay; 8 channels in groups of 1; 5 A per group; diagnostics; substitute value: switching cycle counter...
Cena na upit
SIMATIC S7-1500, digital output module DQ 8xAC 230V/5A ST; relay; 8 channels in groups of 1; 5 A per group; diagnostics; substitute value: switching cycle counter for integrated relay, the module supports the safety-oriented shutdown of load groups up to SIL1 according to EN IEC 62061:2021 and Category 2 / PL c according to EN ISO 13849-1:2015. front connector (screw terminals or push-in) to be ordered separately |
General information | |
Product type designation | DQ 8x230 V AC/5 A ST (relay) |
HW functional status | From FS02 |
Firmware version | V2.1.0 |
● FW update possible | Yes |
Product function | |
● I&M data | Yes; I&M0 to I&M3 |
● Isochronous mode | No |
● Prioritized startup | Yes |
Engineering with | |
● STEP 7 TIA Portal configurable/integrated from version | V12 / V12 |
● STEP 7 configurable/integrated from version | V5.5 SP3 / - |
● PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
● PROFINET from GSD version/GSD revision | V2.3 / - |
Operating mode | |
● DQ | Yes |
● DQ with energy-saving function | No |
● PWM | No |
● Oversampling | No |
● MSO | Yes |
● Integrated operating cycle counter | Yes; FW V2.1.0 or higher |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current | |
Current consumption, max. | 80 mA |
output voltage / header | |
Rated value (AC) | 230 V; 24 V DC to 120 V DC / 24 V AC to 230 V AC |
Power | |
Power available from the backplane bus | 0.8 W |
Power loss | |
Power loss, typ. | 5 W |
Digital outputs | |
Type of digital output | Relays |
Number of digital outputs | 8 |
Current-sinking | Yes |
Current-sourcing | Yes |
Digital outputs, parameterizable | Yes |
Short-circuit protection | No |
Controlling a digital input | Yes; possible |
Size of motor starters according to NEMA, max. | 5 |
Switching capacity of the outputs | |
● on lamp load, max. | 1 500 W; 10 000 operating cycles |
● Low energy/fluorescent lamps with electronic control gear | 10x 58 W (25 000 operating cycles) |
● Fluorescent tubes, conventionally compensated | 1x 58 W (25 000 operating cycles) |
● Fluorescent tubes, uncompensated | 10x 58 W (25 000 operating cycles) |
Output current | |
● for signal "1" rated value | 5 A |
● for signal "1" permissible range, min. | 5 mA; 10 V |
● for signal "1" permissible range, max. | 8 A; thermal continuous current |
● for signal "0" residual current, max. | 0 A |
Parallel switching of two outputs | |
● for logic links | Yes |
● for uprating | No |
● for redundant control of a load | Yes |
Switching frequency | |
● with resistive load, max. | 2 Hz |
● with inductive load, max. | 0.5 Hz |
● on lamp load, max. | 2 Hz |
Total current of the outputs | |
● Current per channel, max. | 8 A; see additional description in the manual |
● Current per group, max. | 8 A; see additional description in the manual |
● Current per module, max. | 64 A; see additional description in the manual |
Relay outputs | |
● Number of relay outputs | 8 |
● Rated supply voltage of relay coil L+ (DC) | 24 V |
● Current consumption of relays (coil current of all relays), typ. | 80 mA |
● external protection for relay outputs | With miniature circuit breaker with characteristic B for: cos φ 1.0: 600 A cos φ 0.5 ... 0.7: 900 A with 8 A Diazed fuse: 1 000 A |
● Contact connection (internal) | No |
● Number of operating cycles, max. | 4 000 000; see additional description in the manual |
● Relay approved acc. to UL 508 | Yes; 250 V AC/5 A g.p.; 120 V AC TV-4 tungsten; A300, R300 |
Switching capacity of contacts | |
— with inductive load, max. | see additional description in the manual |
— with resistive load, max. | see additional description in the manual |
Cable length | |
● shielded, max. | 1 000 m |
● unshielded, max. | 600 m |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Substitute values connectable | Yes |
Alarms | |
● Diagnostic alarm | Yes |
Diagnoses | |
● Monitoring the supply voltage | Yes |
● Wire-break | No |
● Short-circuit | No |
Diagnostics indication LED | |
● RUN LED | Yes; green LED |
● ERROR LED | Yes; red LED |
● MAINT LED | Yes; Yellow LED |
● Monitoring of the supply voltage (PWR-LED) | Yes; green LED |
● Channel status display | Yes; green LED |
● for channel diagnostics | No |
● for module diagnostics | Yes; red LED |
Potential separation | |
Potential separation channels | |
● between the channels | Yes; Switching of different phases permitted |
● between the channels, in groups of | 1 |
● between the channels and backplane bus | Yes |
● Between the channels and load voltage L+ | Yes |
Permissible potential difference | |
between different circuits | 250 V AC between the channels and the supply voltage L+, 250 V AC between the channels and the backplane bus; 250 V AC between the channels (500 V AC when connecting different phases; basic insulation) |
Isolation | |
Isolation tested with | between the channels: 3 100 V DC; between the channels and the backplane bus: 3 100 V DC; between the channels and the supply voltage L+: 3 100 V DC; between the L+ and the backplane bus: 707 V DC (type test) |
Standards, approvals, certificates | |
Suitable for safety functions | No |
Suitable for safety-related tripping of standard modules | Yes; From FS03 |
Highest safety class achievable for safety-related tripping of standard modules | |
● Performance level according to ISO 13849-1 | PL c |
● Category according to ISO 13849-1 | Cat. 2 |
Ambient conditions | |
Ambient temperature during operation | |
● horizontal installation, min. | -30 °C; From FS03 |
● horizontal installation, max. | 60 °C |
● vertical installation, min. | -30 °C; From FS03 |
● vertical installation, max. | 40 °C |
Dimensions | |
Width | 35 mm |
Height | 147 mm |
Depth | 129 mm |
Weights | |
Weight, approx. | 350 g |
last modified: | 7/28/2021 |
Slicni proizvodi:
Siemens S7-1500, DQ 8x230VAC/2A ST (Triac); 6ES7522-5FF00-0AB0
SIMATIC S7-1500, digital output module DQ 8x230 V AC/2 A ST; TRIAC; 8 channels in groups of 1; 2 A per group; Substitute value: Front connector (screw terminals
-
(Trenutno nema na stanju)
Cena na upit
Siemens S7-1500, DQ 32x24VDC/0.5A HF; 6ES7522-1BL01-0AB0
SIMATIC S7-1500, digital output module DQ 32x24V DC/0.5A HF; 32 channels in groups of 8; 4 A per group; single-channel diagnostics; substitute value, switching cycle
-
(Trenutno nema na stanju)
Cena na upit
Siemens S7-1500, DQ 32x24VDC/0.5A BA; 6ES7522-1BL10-0AA0
SIMATIC S7-1500, digital output module, DQ32xDC 24V/0.5A BA, 32 channels in groups of 8, 4 A per group; the module supports the safety-oriented shutdown of load
-
(Trenutno nema na stanju)
Cena na upit
Siemens S7-1500, DQ 16x24V DC/0.5A HF; 6ES7522-1BH01-0AB0
SIMATIC S7-1500, digital output module DQ16x24 V DC/0.5A HF; 16 channels in groups of 8; 4 A per group; single-channel diagnostics; substitute value: switching cycle
-
(Trenutno nema na stanju)
Cena na upit
Siemens S7-1500, DQ 16x24VDC/0.5A BA; 6ES7522-1BH10-0AA0
SIMATIC S7-1500, digital output module, DQ16xDC 24V/0.5A BA, 16 channels in groups of 8, 4 A per group; the module supports the safety-oriented shutdown of load
-
(Trenutno nema na stanju)
Cena na upit
Siemens S7-1500, DQ 8x24VDC/2A HF; 6ES7522-1BF00-0AB0
SIMATIC S7-1500, digital output module DQ 8x24 V DC/2A HF; 8 channels in groups of 8; 8 A per group; diagnostics; substitute value: 2 channels can be used for pulse
-
(Trenutno nema na stanju)
Cena na upit