Siemens SIMATIC PM1507/1AC/24VDC/3A; 6EP1332-4BA00
SIMATIC PM1507/1AC/24VDC/3A SIMATIC PM 1507 24 V/3 A Stabilized power supply for SIMATIC S7-1500 input: 120/230 V AC, output: 24 V DC/3 A...
Cena na upit
SIMATIC PM1507/1AC/24VDC/3A
SIMATIC PM 1507 24 V/3 A Stabilized power supply for SIMATIC S7-1500 input: 120/230 V AC, output: 24 V DC/3 A
SIMATIC PM 1507 24 V/3 A Stabilized power supply for SIMATIC S7-1500 input: 120/230 V AC, output: 24 V DC/3 A
Input | |
type of the power supply network | 1-phase AC |
supply voltage at AC | |
● initial value | Automatic range selection |
supply voltage | |
● 1 at AC rated value | 120 V |
● 2 at AC rated value | 230 V |
input voltage | |
● 1 at AC | 85 ... 132 V |
● 2 at AC | 170 ... 264 V |
design of input wide range input | No |
overvoltage overload capability | 2.3 × Vin rated, 1.3 ms |
operating condition of the mains buffering | at Vin = 93/187 V |
buffering time for rated value of the output current in the event of power failure minimum | 20 ms |
operating condition of the mains buffering | at Vin = 93/187 V |
line frequency | |
● 1 rated value | 50 Hz |
● 2 rated value | 60 Hz |
line frequency | 45 ... 65 Hz |
input current | |
● at rated input voltage 120 V | 1.4 A |
● at rated input voltage 230 V | 0.8 A |
current limitation of inrush current at 25 °C maximum | 23 A |
duration of inrush current limiting at 25 °C | |
● maximum | 3 ms |
I2t value maximum | 1.3 A²·s |
fuse protection type | T 3,15 A/250 V (not accessible) |
● in the feeder | Recommended miniature circuit breaker: 10 A characteristic B or 6 A characteristic C |
Output | |
voltage curve at output | Controlled, isolated DC voltage |
output voltage at DC rated value | 24 V |
output voltage | |
● at output 1 at DC rated value | 24 V |
relative overall tolerance of the voltage | 1 % |
relative control precision of the output voltage | |
● on slow fluctuation of input voltage | 0.1 % |
● on slow fluctuation of ohm loading | 0.1 % |
residual ripple | |
● maximum | 50 mV |
voltage peak | |
● maximum | 150 mV |
product function output voltage adjustable | No |
display version for normal operation | LED green for 24 V OK; LED red for error; LED yellow for stand-by |
behavior of the output voltage when switching on | No overshoot of Vout (soft start) |
response delay maximum | 1.5 s |
voltage increase time of the output voltage | |
● typical | 10 ms |
output current | |
● rated value | 3 A |
● rated range | 0 ... 3 A |
supplied active power typical | 72 W |
short-term overload current | |
● on short-circuiting during the start-up typical | 12 A |
● at short-circuit during operation typical | 12 A |
duration of overloading capability for excess current | |
● on short-circuiting during the start-up | 70 ms |
● at short-circuit during operation | 70 ms |
product feature | |
● bridging of equipment | Yes |
number of parallel-switched equipment resources for increasing the power | 2 |
Efficiency | |
efficiency in percent | 87 % |
power loss [W] | |
● at rated output voltage for rated value of the output current typical | 11 W |
Closed-loop control | |
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical | 0.1 % |
relative control precision of the output voltage load step of resistive load 50/100/50 % typical | 1 % |
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical | 3 % |
setting time | |
● load step 10 to 90% typical | 5 ms |
● load step 90 to 10% typical | 5 ms |
● maximum | 5 ms |
Protection and monitoring | |
design of the overvoltage protection | Additional control loop, limitation (closed loop control) at < 28.8 V |
response value current limitation | 3.15 ... 3.6 A |
response value current limitation typical | 3.4 A |
property of the output short-circuit proof | Yes |
design of short-circuit protection | Electronic shutdown, automatic restart |
display version for overload and short circuit | - |
Safety | |
galvanic isolation between input and output | Yes |
galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 and EN 61131-2 |
operating resource protection class | Class I |
leakage current | |
● maximum | 3.5 mA |
● typical | 0.4 mA |
protection class IP | IP20 |
Approvals | |
certificate of suitability | |
● CE marking | Yes |
● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 |
● CSA approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 |
● cCSAus, Class 1, Division 2 | No |
● ATEX | Yes; ATEX (EX) II 3G Ex nA nC IIC T4 Gc |
certificate of suitability | |
● relating to ATEX | IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cULus (ANSI/ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455 |
● IECEx | Yes; IECEx Ex nA nC IIC T4 Gc |
● NEC Class 2 | No |
● ULhazloc approval | Yes |
● FM registration | Yes; Class I, Div. 2, Group ABCD, T4 |
type of certification CB-certificate | Yes |
certificate of suitability | |
● EAC approval | Yes |
certificate of suitability shipbuilding approval | Yes |
shipbuilding approval | ABS, BV, DNV GL |
Marine classification association | |
● American Bureau of Shipping Europe Ltd. (ABS) | Yes |
● French marine classification society (BV) | Yes |
● DNV GL | Yes |
● Lloyds Register of Shipping (LRS) | No |
● Nippon Kaiji Kyokai (NK) | No |
EMC | |
standard | |
● for emitted interference | EN 55022 Class B |
● for mains harmonics limitation | EN 61000-3-2 |
● for interference immunity | EN 61000-6-2 |
environmental conditions | |
ambient temperature | |
● during operation | 0 ... 60 °C; with natural convection |
● during transport | -40 ... +85 °C |
● during storage | -40 ... +85 °C |
environmental category according to IEC 60721 | Climate class 3K3, 5 … 95% no condensation |
Mechanics | |
type of electrical connection | Screw-/spring clamp connection |
● at input | L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² |
● at output | L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm² |
product function | |
● removable terminal at input | Yes |
● removable terminal at output | Yes |
width of the enclosure | 50 mm |
height of the enclosure | 147 mm |
depth of the enclosure | 129 mm |
required spacing | |
● top | 40 mm |
● bottom | 40 mm |
● left | 0 mm |
● right | 0 mm |
net weight | 0.45 kg |
product feature of the enclosure housing can be lined up | Yes |
fastening method | Can be mounted onto S7-1500 rail |
MTBF at 40 °C | 1 611 993 h |
other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
Slicni proizvodi:
Siemens SIMATIC PM1507/1AC/24VDC/8A; 6EP1333-4BA00
SIMATIC PM1507/1AC/24VDC/8A SIMATIC PM 1507 24 V/8 A Regulated power supply for SIMATIC S7-1500 input: 120/230 V AC, output: 24 V DC/8 A
-
(Trenutno nema na stanju)
Cena na upit
Siemens Universal Front Door S7-1500 IO(25mm); 6ES7528-0AA00-0AA0
SIMATIC S7-1500, spare part Front door for 25 mm width I/O modules; Consisting of: * Front door (unlasered), * Labeling strips (front) * Wiring diagram, 5 units
-
(Trenutno nema na stanju)
Cena na upit
Siemens S7-1500, PS 25W 24V DC; 6ES7505-0KA00-0AB0
SIMATIC S7-1500, System power supply PS 25W 24 V DC, supplies the backplane bus of the S7-1500 with operating voltage
-
(Trenutno nema na stanju)
Cena na upit
Siemens SIMATIC S7-1500, Front connector in push-in design, 40-pole, for 35 mm wide modules; 6ES7592-1BM00-0XB0
SIMATIC S7-1500, Front connector in push-in design, 40-pole, for 35 mm wide modules incl. 4 potential bridges and cable ties
-
(Trenutno nema na stanju)
4.608,55